610.44521.40.000
28 / 52
© Gardner Denver Deutschland GmbH
Installation
Connection
3/PE AC, 320 V ... 550V, 45 ... 65 Hz
X1
L3
L2
L1
K14 K12 K11
PES
PES
4.3 mm
1.2...1.5 Nm
10.7...13.3 lb-in
6 mm
1.1 Nm
9.7 lb-in
ne2bhxn431
Fig. 14: Connectiing frequency inverter 2FC4302-1NE00 ... 2FC4752-1NE00
1 Connecting the mains cable:
A Pass the mains cable through the cable gland.
B Attach the ring cable lug (Ø 4.3 mm) to the
PE conductor.
C Screw the PE conductor onto the PE stud for
the mains cable:
–
observe tightening torque
D Connect cores L1, L2 and L3 to X1 in correct
phase relation:
–
observe tightening torque!
2 Wiring the relay output (if necessary):
A Pass the cable through the cable gland.
B Connect the shield of shielded cables
according to EMC requirements (
26).
C Connect cores to terminal X1:
–
observe terminal connection diagram and
tightening torque!
3 Connecting the control cable shield:
A Pass the control cable through the cable
gland.
B Connect the shield according to EMC
requirements (
26).
C Control cable connection: ( (
28)
4 Tighten all cable glands.
4.4.5 Wiring of control connections
The control connections are on the control
terminal module 2FX4501−0NE00 which is
included in the scope of supply.
Install the control terminal module in the terminal
box of the frequency inverter before starting to
wire the control connections.
62 7
7
8 9
20 28 E1 E2 E3 E4 39 A1 59
X3
n_e2fx1006
Fig. 15: Control connections 2FX4501-0NE00
Mount control terminal module
CAUTION
If the cap is plugged on the socket
connector when assembling the frequency
inverter, the control terminal module will be
damaged!
Remove the cap from the socket connector
at the control terminal module.
Keep the cap.