beautypg.com

Cla-val – Cla-Val 390-07/3690-07 User Manual

Page 27

background image

Troubleshooting FAQ

LED Diagnostics

When power is applied to the actuator, the LED will be red for
approximately 5-30 seconds, and then will change to solid green.

Green

OK.

No light

Check power supply.

Red

High torque limit has been exceeded - Power down and power up
again
Excessive Voltage has been applied (Above 32 Volts).

Blinking red/green

Calibration was not completed - recalibrate

Changing set-point without a 4-20 mA command signal
with the USB cable connected to

Go to ‘Display’ tab and select Milliamp value and check the box to
activate.

Changing set-point without a command signal without
an e-Drive - USB cable.

Refer to wiring diagram.
To Increase Actuator connect the Purple Wire with the Pink.
To Decrease Actuator connect the turquoise Wire with the Pink.

To Increase or Decrease the actuator without 4-20 mA
signal.

Refer to wiring diagram in the this manual. To increase actuator
connect the purple wire to the pink. To decrease actuator, connect
the turquoise wire to the pink.

What are the default settings for the 130VC-3 actuator?

Factory default setting for 130VC-3 Actuator range parameter is
the full pilot spring range scaled to match the 4 to 20 mA Remote
Command Input analog signal. Factory default setting for 130VC-3
Actuator rotation speed is one rpm with 24 VDC power.

How do I get the software to work with the actuator?

To set up a link with 130VC-3 Actuator, first install cable driver and
then the special multi-USB communications cable. After installing
driver and communication cable, the Actuator must be powered for
link to work. Follow wiring diagram and hardware hookup instruc-
tions. Download Wiring Diagram from website (www.cla-val.com).

How do I install Special USB Communication Cable?

When 130VC-3 communications cable is installed in your laptop
computer USB port for the first time, Windows will search your
computer for the cable USB driver. If Windows Plug and Play does

not automatically find the driver and connect to actuator, then the
cable driver must be set up manually. Windows will take you step-
by-step through the manual set up process. The cable USB driver
is installed during software download. You will have to browse to
the Cla-Val folder created during download where the driver file is
located. Details are in this manual.

My computer does not have a USB port

Older laptop computers with only Serial port may have a problem
using USB to Serial adapter with special USB connector cable and
communicating with 130VC-3 actuator. Make sure the USB to
Serial adapter cable is less than 18 inches long. Also, USB exten-
sion cables should not be used because they will degrade signals
and cause problems. If problem persists, consult Cla-Val factory
technical support.

Why is actuator LED still blinking red/green after I
downloaded the settings?

Once the calibration mode button is activated, all steps must be
done before downloading is begun. Actuator LED will show green
when downloading is successful and complete.

Can I make a file ahead of time and download it to
130VC-3 later?

All hardware hookup steps must be completed before program will
communicate and change 130VC-3 parameters. Until wiring and
power connections are made to the actuator, this program can be
opened, but new parameters can not be created or stored or sent
to the actuator. Changes to parameters must be done "live" and
while control valve is operating. Actuator LED will show green
when downloading is successful and complete.
.

GENERAL DISCLAIMER

In accordance with our policy of continuous development and
improvement, CLA-VAL reserves the right to modify or improve its
products at any time without prior notice. CLA-VAL assumes no lia-
bility or responsibility for any errors or omissions in the content of
this document.

CLA-VAL EUROPE

Chemin des Mésanges 1

CH-1032 Romanel/
Lausanne, Switzerland
Phone: 41-21-643-15-55
Fax: 41-21-643-15-50
E-mail: [email protected]

CLA-VAL FRANCE

Porte du Grand Lyon 1
ZAC du Champ du Périer
France - 01700 Neyron
Phone: 33-4-72-25-92-93
Fax: 33-4-72-25-04-17
E-mail: [email protected]

CLA-VAL

PO Box 1325 Newport Beach CA 92659-0325

800-942-6326

Fax: 949-548-5441

Web Site: cla-val.com

E-mail: [email protected]

©

COPYRIGHT CLA-VAL 2009 Printed in USA Specifications subject to change without notice.

CLA-VAL CANADA

4687 Christie Drive
Beamsville, Ontario
Canada L0R 1B4
Phone: 905-563-4963
Fax: 905-563-4040
E-mail [email protected]

CLA-VAL UK

Dainton House, Goods Station Road
Tunbridge Wells
Kent TN1 2 DH England
Phone: 44-1892-514-400
Fax: 44-1892-543-423
E-mail: [email protected]

N-130VC-3