beautypg.com

Vent reducer, Venting, Multiple heater manifold – John Wood Commercial Atmospheric Vent - AJWSM User Manual

Page 9: Water line connections

background image

9

CONFINED SPACE
When drawing combustion and dilution air from inside a conventionally

constructed building to a confined space, such a space shall be

provided with two permanent openings, ONE IN OR WITHIN 12

INCHES (30.5cm) OF THE ENCLOSURE TOP AND ONE IN OR

WITHIN 12 INCHES (30.5cm) OF THE ENCLOSURE BOTTOM.

Each opening shall have a free area of at least one square inch per

1000 Btuh (2,225mm

2

/kW) of the total input of all appliances in the

enclosure, but not less than 100 square inches (645 square cm).
If the confined space is within a building of tight construction, air for

combustion, ventilation, and draft hood dilution must be obtained

from outdoors. When directly communicating with the outdoors

or communicating with the outdoors through vertical ducts, two

permanent openings, located in the above manner, shall be provided.

Each opening shall have a free area of not less than one square inch

per 4000 Btuh (8,900mm

2

/kW) of the total input of all appliances in the

enclosure. If horizontal ducts are used, each opening shall have a

free area of not less than one square inch per 2000 Btuh (4,450mm

2

/

Kw) of the total input of all appliances in the enclosure.

VENT REDUCER

The (A)JWSM65250, & (A)JWSM100275 are shipped with an 8”

to 6” diameter flue outlet adapter. Each adapter fits on top of the

installed flue damper. Use only vent reducers supplied with the

unit. The venting must comply with the NATIONAL FUEL GAS

CODE, ANSI Z223.1/NFPA 54.

FIGURE 7

VENTING

WARNING

THE INSTRUCTIONS IN THIS SECTION ON VENTING MUST

BE FOLLOWED TO AVOID CHOKED COMBUSTION OR RE-

CIRCULATION OF FLUE GASES. SUCH CONDITIONS CAUSE

SOOTING OR RISKS OF FIRE AND ASPHYXIATION.

Heater must be protected from freezing downdrafts.
Remove all soot or other obstructions from the chimney that will

retard a free draft.
Type B venting is recommended with these heaters. See table 3

TECHNICAL DATA VENTING.
This water heater must be vented in compliance with all local

codes, the current edition of the National Fuel Gas Code (ANSI-

Z223.1) or The Natural Gas and Propane Installation Code (CAN/

CSA B149.1) and with the Category I Venting Tables.
If any parts of the vent system are exposed to ambient

temperatures below 35 degrees F (2 degrees C) they must be

insulated to prevent condensation.
• Do not connect the heater to a common vent or chimney with

solid fuel burning equipment. This practice is prohibited by

many local building codes as is the practice of venting gas

fired equipment to the duct work of ventilation systems.

• Where a separate vent connection is not available and the vent

pipe from the heater must be connected to a common vent with

an oil burning furnace, the vent pipe should enter the smaller

common vent or chimney at a point above the large vent pipe.

FIGURE 8

FIGURE 9

MULTIPLE HEATER MANIFOLD

Figure 10 and table 3 should be used for horizontally manifolding

two or more heaters. Also see MULTIPLE-UNIT INSTALLATIONS of

MECHANICAL VENTING section for induced draft applications.

FIGURE 10

WATER LINE CONNECTIONS

This manual provides detailed installation diagrams (see pages

16-22 of this manual) for typical methods of application for the

water heaters.

The water heater may be installed by itself, or with a separate

storage tank, on both single and two-temperature systems.

When used with a separate storage tank, the circulation may

be either by gravity or by means of a circulating pump. When a

circulating pump is used it is important to note that the flow rate

should be slow so that there will be a minimum of turbulence

inside the heater.

CREATED BY NEEVIA DOCUSTAMP TRIAL VERSION (WWW.NEEVIA.COM)

CREATED BY NEEVIA DOCUSTAMP TRIAL VERSION (WWW.NEEVIA.COM)

This manual is related to the following products: