beautypg.com

Technical data venting, table 3 – John Wood Commercial Atmospheric Vent - AJWSM User Manual

Page 10

background image

10

TYPE B GAS VENT

Multiple Gas Fired Tank-Type Heaters

When venting mutiple tank type heaters using Type B

vent pipe, follow the installation diagram (figure 8) and

tables below which give sizing and data based upon

NFPA 54/ANSI Z223.

TECHNICAL DATA VENTING, TABLE 3

MODEL JWSM71120

Input: 120,000 Btuh Total Vent Height (Feet)

Draft Hood: 5”

6

8

10

15

20

30

50

100

Input Btuh

Rise

Vent Connector Diameter (inches)

120,000

1 Ft.

7

7

7

6

6

6

6

6

120,000

2 Ft.

6

6

6

6

6

6

6

5

123,000

3 Ft.

6

6

6

6

6

5

5

5

Number of Heaters

Combined Input in

Thousands of Btuh

Manifold and Common Vent Diameter (In inches)

2

3

4

240

10

8

8

7

7

7

6

7

360

10

10

10

10

8

8

7

7

480

12

12

12

10

10

10

8

8

MODEL JWSM95199, JWSM76199, & (A)JWSM100199
Input: 199,000 Btuh
Total Vent Height (Feet)

Draft Hood: 6”

6

8

10

15

20

30

50

100

Input Btuh

Rise

Vent Connector Diameter (in inches)

199,000

-

-

8

8

8

8

8

7

199,000

8

8

8

8

7

7

7

7

190,000

8

7

7

7

7

7

6

6

197,000

8

7

7

7

7

7

7

6

199,000

8

8

7

7

7

7

7

6

Number of Heaters

Combined Input in

Thousands of Btuh

Manifold & Common Vent Diameter

2

358

10

10

10

10

8

8

7

7

380

12

10

10

10

10

8

7

7

394/398

12

10

10

10

10

8

8

7

3

537

14

12

12

12

10

10

10

8

570

14

12

12

12

10

10

10

10

591/597

14

14

12

12

12

10

10

10

4

716

14

14

14

12

12

12

10

10

760

16

14

14

14

12

12

10

10

788/796

16

14

14

14

12

12

12

10

CREATED BY NEEVIA DOCUSTAMP TRIAL VERSION (WWW.NEEVIA.COM)

CREATED BY NEEVIA DOCUSTAMP TRIAL VERSION (WWW.NEEVIA.COM)

This manual is related to the following products: