ONE OR TWO TEMPERATURE - ONE HEATERS,HIGH TEMPERATURE
STORAGE WITH OR WITHOUT RECIRCULATION
HEATER WITH OR WITHOUT MIXING VALVE
HEATER WITH MIXING VALVE AND RECIRCULATED SANITIZING LOOP
NOTE 1: TOGGLE SWITCH CONTROLS 180°F (82°C)
WATER CIRCULATION. INSTALL ON OR
CLOSE TO DISHWASHING MACHINE. TOGGLE
SWITCH MUST BE CLOSED (ON) DURING THE
RINSE OPERATION AND OPEN (OFF) WHEN
DISHWASHER IS NOT OPERATING OR WHEN
ON LONG STANDBY.
NOTE 2: INSTALL LINE TEMPERATURE CONTROL
IN AN UNINSULATED TEE BEYOND THE
DISHWASHING MACHINE TAKEOFF
IN THE SANITIZING LOOP. CONTROL
SHOULD BE SET AT 185°F (85°C).
NOTE 3: ADJUST PLUG COCK SO THE SANITIZING
LOOP FLOW RATE DOES NOT CAUSE
UNNECESSARY TURBULENCE IN THE
TANK.
* PIPE RELIEF VALVE TO OPEN DRAIN.
INSTALL IN ACCORDANCE WITH LOCAL
CODES.
CIRCULATING RETURN LINE CONNECTIONS.
- T E M P E R E D WAT E R L O O P, I F U S E D ,
CONNECT TO POINT “R”.
- STORED TEMPERATURE WATER LOOP, IF USED,
CONNECT TO COLD WATER INLET.
CAUTION: IF BUILDING COLD WATER SUPPLY HAS A BACKFLOW
PREVENTER, CHECK VALVE OR WATER METER WITH CHECK VALVE,
PROVISIONS FOR THERMAL EXPANSION OF WATER IN THE HOT WATER
SYSTEM MUST BE PROVIDED.
DANGER
TEMPERATURE SETTING SHOULD NOT
EXCEED SAFE USE TEMPERATURE AT
FIXTURES. SEE WATER TEMPERATURE
CONTROL WARNING ON PAGE 25. IF HIGHER
PREHEAT TEMPERATURES ARE NECESSARY
TO OBTAIN ADEQUATE BOOSTER OUTPUT,
ADD AN ANTI-SCALD VALVE FOR HOT WATER
SUPPLIED TO FIXTURES.