PIN END VIEW

24 V.A.C.

NORMAL SEQUENCE OF OPERATION

B. DAMPER HAS OPENED,

NO COMBUSTION

VOLTAGE ACROSS:

4 & 1; 4 & 2; 4 & 3:

1. Check for power at ignition module terminals. If 24VAC power is present damper

is working properly.

2. Defective component in appliance after the flue damper.

3. If 24 VAC is not present at the ignition module, look for loose or broken

connections between damper and ignition module.

4. If the connections from damper to ignition module seem proper, replace damper

assembly. If a damper assembly is not available, place the service switch in the

hold open position. This should keep the damper in the open position and allow

the customer to have automatic heat, until a replacement damper can be installed.

C. DAMPER ROTATES

CONTINUOUSLY

Change the entire damper assembly

D. DAMPER STICKS

1. Make sure no screws obstruct the damper blade.

2. Make sure damper pipe assembly is not egg shaped.

3. Make sure damper rod is not rubbing on pipe assembly.

See figure on front page of this insert sheet

ABNORMAL OPERATION

A. NOTHING WORKING

NO VOLTAGE ACROSS:

4 & 1

1. High Limit has tripped and is OPEN. Determine reason for tripping of high limit

2. Bad Transformer

3. Loose or broken connections

4. Blown fuse or circuit breaker

5. Disconnect switch off

6. Harness not plugged into appliance receptacle

A. FLUE DAMPER OPEN OR OPENING

(Unit is calling for heat and damper disc should be in vertical position)

VOLTAGE ACROSS:

4 & 1

All Times that High Limit is closed

4 & 2

Calling for Heat

Open or Opening

4 & 3

During Combustion

Damper Open+

B.

FLUE DAMPER CLOSED (Unit is not calling for heat and damper disc should be in horizontal position)

NOTE: POSITION 4 IS COMMON AND POSITION 3 IS HOT 24VAC

VOLTAGE ACROSS:

4 & 1

All Times that High Limit is closed

NO VOLTAGE ACROSS:

4 & 3 or 4 & 2

1.Thermostat not calling for heat.

EFFIKAL RVGP-KSF-SERIES FLUE DAMPER TROUBLE SHOOTING GUIDE

Do not turn damper open manually or motor damage will result, use the service switch.

All readings are taken from harness receptacle. Do not push meter leads into harness receptacle.

This opens the pins and will create connection problems.

WARNING

Do not negate the action

of any existing safety

or operational controls.

IMPORTANT: DAMPER MUST BE OPEN BEFORE COMBUSTION TAKES PLACE. If all steps have been

tried and damper problems persists call Product Service and Support 800-456-9805.

NOTE: DAMPER DISC SHOWN IN OPEN POSITION.

Effikal Pinouts

Adapter wire

& wire colors

Function

colors in*

1. Brown

24 VAC HOT

Black

2. Orange

Signal In

Yellow

3. Yellow

Signal Out

Red

4. Black

24 VAC Common

White

*See Connection Diagram, Figure 14.