beautypg.com

Operation, Important, General – John Wood Commercial Atmospheric Vent - AJWSM User Manual

Page 22: Filling

background image

22

OPERATION

IMPORTANT

A qualified person must perform the initial firing of the heater. At

this time the user should not hesitate to ask the individual any

questions which they may have in regard to the operation and

maintenance of the unit.

An Operational Checklist is included at the rear of this manual. By

using this checklist the user may be able to make minor operational

adjustments and avoid unnecessary service calls. However, the

user should not attempt repairs which are not listed under the

USER column.

GENERAL

NEVER OPERATE THE HEATER WITHOUT FIRST BEING

CERTAIN IT IS FILLED WITH WATER AND A TEMPERATURE

AND PRESSURE RELIEF VALVE IS INSTALLED IN THE RELIEF

VALVE OPENING OF THE HEATER.

SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL

TO SHUT OFF, TURN OFF THE MANUAL GAS CONTROL VALVE

TO THE APPLIANCE.

CAUTION

Before proceeding with the operation of the unit make sure

the water heater and system are filled with water and all air is

expelled.

FILLING

1. Close the heater drain valve by turning handle clockwise.

2. Open a nearby hot water faucet to permit the air in the system

to escape.

3. Fully open the cold water inlet pipe valve allowing the heater

and piping to be filled.

4. Close the hot water faucet as water starts to flow.

5. The heater is ready to be operated.

PURGING

Gas line purging is required with new piping or systems in which

air has entered.

CAUTION

PURGING SHOULD BE PERFORMED BY PERSONS

EXPERIENCED IN THIS TYPE GAS SERVICE. TO AVOID RISK OF

FIRE OR EXPLOSION, PURGE DISCHARGE MUST NOT ENTER

CONFINED AREAS OR SPACES WHERE IGNITION CAN OCCUR.

THE AREA MUST BE WELL VENTILATED AND ALL SOURCES OF

IGNITION MUST BE INACTIVATED OR REMOVED.

WARNING

THE GAS VALVE MUST HAVE BEEN IN THE OFF POSITION FOR

AT LEAST 5 MINUTES. This waiting period is an important safety

step. Its purpose is to permit gas that may have accumulated in the

combustion chamber to clear. IF YOU DETECT GAS ODOR AT THE

END OF THIS PERIOD DO NOT PROCEED WITH LIGHTING.

RECOGNIZE THAT GAS EVEN IF IT SEEMS WEAK, MAY

INDICATE PRESENCE OF ACCUMULATED GAS SOMEPLACE

IN THE AREA WITH RISK OF FIRE OR EXPLOSION. SEE THE

FRONT PAGE FOR STEPS TO BE TAKEN.

All gas and water lines leak tested and open.

With above conditions satisfied, light the unit in accordance with

the instructions on the Operating label attached to the heater. If

label instructions are not legible - determine which gas valve the

appliance is equipped with and use the applicable

OPERATING

INSTRUCTIONS

as follows:

IF PILOT FLAME GOES OUT

- Main burners will extinguish and

pilot will attempt reignition.

DAMPER MUST BE IN FULL OPEN POSITION FOR PILOT AND/

OR MAIN BURNER IGNITION TO OCCUR - See SEQUENCE

OF OPERATION

for complete description.

Each heater is equipped with a Honeywell Ignition Module. This

module will try to prove pilot for 90 seconds. If pilot is not proven

within the 90 secs, the unit will retry after 5 minutes. This cycle

will continue until pilot is proven.

If pilot does not ignite when system calls for heat, check for

pilot ignition spark at pilot assembly.

Refer to OPERATIONAL

CHECKLIST and EFFIKAL RVGP-KSF SERIES FLUE DAMPER

TROUBLESHOOTING GUIDE.

CREATED BY NEEVIA DOCUSTAMP TRIAL VERSION (WWW.NEEVIA.COM)

CREATED BY NEEVIA DOCUSTAMP TRIAL VERSION (WWW.NEEVIA.COM)

This manual is related to the following products: