beautypg.com

Electronic ignition control, Automatic flue damper device, Circulating pump – John Wood Commercial Atmospheric Vent - AJWSM User Manual

Page 6: Dishwashing machine requirement

background image

6

Continued manual resetting of high limit control, preceded by higher

than usual water temperature is evidence of high limit switch operation.

The following is a possible reason for high limit switch operation:

• A malfunction in the thermostatic controls would allow the gas

valve to remain open causing water temperature to exceed the

thermostat setting. The water temperature would continue to

rise until high limit switch operation.

Contact your dealer or service agent if continued high limit switch

operation occurs.

DIGITAL THERMOSTAT

FIGURE 3

ELECTRONIC IGNITION CONTROL

Each heater is equipped with a Honeywell ignition module. The

solid state ignition control, fig.4, ignites the pilot burner gas by

creating a spark at the pilot assembly. Pilot gas is ignited and

burns during each running cycle. The main burner and pilot gases

are cut off during the OFF cycle. Pilot gas ignition is proven by the

pilot sensor. Main burner ignition will not occur if the pilot sensor

does not first sense pilot ignition.

HONEYWELL IGNITION MODULE

S8600M Continuous Re-Try

FIGURE 4

AUTOMATIC FLUE DAMPER DEVICE

All units are equipped with an automatic flue damper that

reduces heat loss during the OFF cycles.

Each automatic flue damper drive assembly is equipped with a

“Service Switch”, as shown in figure 5.

FIGURE 5

The “Service Switch” has 2 positions: AUTOMATIC

OPERATION and HOLD OPEN DAMPER. For normal

operation the switch should be in the AUTOMATIC

OPERATION position.

If there is a problem with the damper the “Service Switch” can

be placed in the HOLD OPEN DAMPER position. When the

switch is placed in the HOLD OPEN DAMPER position the

damper disc will rotate to the open position and the heater

may be used until vent assembly is repaired or replaced. DO

NOT turn the damper disc manually; damage will occur to

the drive assembly if operated manually. Refer to TESTING

DAMPER OPERATION section of this manual for additional

information.

CIRCULATING PUMP

A circulating pump is used when a system requires a circulating

loop or there is a storage tank used in conjunction with the heater.

Refer to the piping diagrams in this manual for electrical hookup

information and install in accordance with the current edition of

the National Electrical Code NFPA 70.

Only all bronze circulating pump should be used with commercial

water heaters.

Although circulators are oiled and operated by the manufacturer

some circulating pump must be oiled again before operating.

Please refer to manufacturer’s instructions.

DISHWASHING MACHINE REQUIREMENT

These appliances meet the NSF Standard 5 for sanitary

installations when used with leg kit, Part No. 9003425205.

All dishwashing machines meeting the National Sanitation

Foundation requirements are designed to operate

with water flow pressures between 15 and 25 psi (103 kPa

and 173 kPa). Flow pressures above 25 psi (173 kPa),

or below 15 psi (103 kPa), will result in improperly

sanitized dishes. Where pressures are high, a water

pressure reducing or f low regulating control valve

should be used in 180°F (82°C) line to the dishwashing

machine, and should be adjusted to deliver water between

these limits.

CREATED BY NEEVIA DOCUSTAMP TRIAL VERSION (WWW.NEEVIA.COM)

CREATED BY NEEVIA DOCUSTAMP TRIAL VERSION (WWW.NEEVIA.COM)

This manual is related to the following products: