INCH GAGE- 3.5 kPa) SUPPLY GAS PRESSURE. EXPOSURE

TO HIGHER SUPPLY PRESSURE MAY CAUSE DAMAGE

TO THE GAS VALVE WHICH COULD RESULT IN FIRE OR

EXPLOSION. IF OVERPRESSURE HAS OCCURRED SUCH

AS THROUGH IMPROPER TESTING OF GAS LINES OR

EMERGENCY MALFUNCTION OF THE SUPPLY SYSTEM, THE

GAS VALVE MUST BE CHECKED FOR SAFE OPERATION.

MAKE SURE THAT THE OUTSIDE VENTS ON THE SUPPLY

REGULATORS AND THE SAFETY VENT VALVES ARE

PROTECTED AGAINST BLOCKAGE. THESE ARE PARTS

OF THE GAS SUPPLY SYSTEM, NOT THE HEATER. VENT

BLOCKAGE MAY OCCUR DURING ICE STORMS.

IT IS IMPORTANT TO GUARD AGAINST GAS VALVE FOULING

FROM CONTAMINANTS IN THE GAS WAYS. SUCH FOULING

MAY CAUSE IMPROPER OPERATION, FIRE OR EXPLOSION.

IF COPPER SUPPLY LINES ARE USED THEY MUST BE

INTERNALLY TINNED AND CERTIFIED FOR GAS SERVICE.

BEFORE ATTACHING THE GAS LINE, BE SURE THAT ALL GAS

PIPE IS CLEAN ON THE INSIDE.

TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE

GAS SUPPLY LINE, A DIRT LEG (SOMETIMES CALLED

SEDIMENT TRAP OR DRIP LEG) MUST BE INCORPORATED

IN THE PIPING (SEE FIG. 11). THE DIRT LEG MUST BE

READILY ACCESSIBLE AND NOT SUBJECT TO FREEZING

CONDITIONS. INSTALL IN ACCORDANCE WITH

FIGURE 12

RECOMMENDATIONS OF SERVING GAS SUPPLIERS.

REFER TO THE CURRENT EDITION OF THE NATIONAL

FUEL GAS CODE.

To prevent damage, care must be taken not to apply too much

torque when attaching gas supply pipe to gas valve inlet.

Apply joint compounds (pipe dope) sparingly and only to the

male threads of pipe joints. Do not apply compounds to the first

two threads. Use compounds resistant to the action of liquefied

petroleum gases.

GAS PIPING AND DIRT LEG INSTALLATION

FIGURE 11