INSTALLATION DIAGRAMS-TOP INLET/OUTLET USAGE

GENERAL

The type, size and location of the relief valves must be in

accordance with local codes. The locations of the relief valves

shown in the installation diagrams are typical. The heater has a

factory installed high temperature limit switch and temperature

and pressure relief valve.

Cold water lines to heater should be installed as shown in order

to minimize gravity circulation of hot water to building cold water

lines.

A listed temperature and pressure relief valve of adequate capacity

is installed on the heater. The locations shown in the installation

diagrams on the following pages are typical.

The discharge opening of the temperature and pressure relief

valve, located in front of the heater must be piped to an open drain

and should not be subject to freezing temperatures.

Install in accordance with all local codes.

Use of the top inlet water connection requires installation of an inlet

dip tube (refer to figure 11). The tube is supplied in the heater.

Follow caution labels if applying heat to this fitting. Do not allow

pipe dope to contact the plastic tube during installation.

CODE RESTRICTIONS

Use of the top inlet water connection is not permitted on

installations in the state of North Carolina, due to the material of

the tube (Polypropylene). Where such code restrictions exist, use

only lower inlet tank connection. This may also require a heat

trap - check local codes. The “Top Outlet” connection may still be

used on these applications. Plug or cap all unused openings in

the tank before filling with water.

DANGER

TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE

TEMPERATURE AT FIXTURES. SEE WATER TEMPERATURE

CONTROL WARNING ON PAGE 25. IF HIGHER PREHEAT

TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE

BOOSTER OUTPUT, ADD AN ANTI-SCALD VALVE FOR HOT

WATER SUPPLIED TO FIXTURES.

TUBE INLET INSTALLATION

FIGURE 13

BEFORE PLACING THE HEATER IN OPERATION, CHECK FOR

GAS LEAKAGE.

Use soap and water solution or other material

acceptable for the purpose in locating the leaks.

DO NOT USE

MATCHES, CANDLES, FLAME OR OTHER SOURCES OF

IGNITION FOR THIS PURPOSE.

DISCONNECT THE HEATER AND ITS MANUAL GAS

SHUT-OFF VALVE FROM THE GAS SUPPLY PIPING

SYSTEM DURING ANY SUPPLY PRESSURE TESTING

EXCEEDING 1/2 PSIG (3.5 kPa). GAS SUPPLY LINE

MUST BE CAPPED WHEN DISCONNECTED FROM

THE HEATER FOR TEST PRESSURES OF 1/2 PSIG

(3.5 kPa) OR LESS. THE APPLIANCE NEED NOT BE

DISCONNECTED, BUT MUST BE ISOLATED FROM THE

SUPPLY PRESSURE TEST BY CLOSING THE MANUAL GAS

Shut-off VALVE.

GAS METER SIZE — NATURAL GASES ONLY

Be sure the gas meter has sufficient capacity to supply the full

rated gas input of the water heater as well as the requirements of

all other gas fired equipment supplied by the meter. If gas meter

is too small, ask the gas company to install a larger meter having

adequate capacity.

GAS PRESSURE REGULATOR

The gas pressure regulator is built into the gas valve and is

equipped to operate on the gas specified on model and rating

plate. The regulator is factory adjusted to deliver gas to burner

at correct water column pressure allowing for a nominal pressure

drop through the controls.

The minimum gas supply pressure for input adjustment must not

be less than 4.5” w.c. (1.12 kPa) for natural gas and 11.0” w.c.

(2.74 kPa) for propane gas.

Do not subject the combination gas valve to inlet gas

pressures of more than 14.0” W.C. (3.48 kPa) - natural gas,

14.0” W.C. (3.48 kPa)- propane gas. A service regulator is

necessary if higher gas pressures are encountered.

Gas pressure specified in Table 5, refer to flow pressure taken at

pressure tap of automatic gas valve while heater is operating.

GROUNDING INSTRUCTIONS

This water heater must be connected to a grounded metal,

permanent wiring system; or an equipment grounding conductor

must be run with the circuit conductors and connected to the

equipment grounding terminal or lead on the water heater.

HEATER WIRING

All electrical work must be installed in accordance with the current

edition of the National Electrical Code NFPA 70 and must conform

to all local code authority having jurisdiction.

AN ELECTRICAL

GROUND IS REQUIRED TO REDUCE RISK OF ELECTRICAL

SHOCK OR POSSIBLE ELECTROCUTION.

If any of the original wire as supplied with the appliance must be

replaced, use only type 105°C thermoplastic or equivalent. 250°C

type F must be used for the flame sensor leads and the spark

ignition cable must be high voltage 250°C.