beautypg.com

Installation instructions, Leveling, Clearances – John Wood Commercial Atmospheric Vent - AJWSM User Manual

Page 7: Required ability, Uncrating, Locating the heater

background image

7

NEVER BE PLACED ON OR ADJACENT TO THE HEATER. OPEN

CONTAINERS OR FLAMMABLE MATERIAL SHOULD NOT BE

STORED OR USED IN THE SAME ROOM WITH THE HEATER.

THE HEATER MUST NOT BE LOCATED IN AN AREA WHERE

IT WILL BE SUBJECT TO FREEZING.

LOCATE IT NEAR A FLOOR DRAIN. THE HEATER SHOULD

BE LOCATED IN AN AREA WHERE LEAKAGE FROM THE

HEATER OR CONNECTIONS WILL NOT RESULT IN DAMAGE

TO THE ADJACENT AREA OR TO LOWER FLOORS OF THE

STRUCTURE.

When such locations cannot be avoided, it is recommended that

a suitable drain pan, adequately drained, be installed under the

appliance.

Water heater life depends upon water quality, water pressure

and the environment in which the water heater is installed. Water

heaters are sometimes installed in locations where leakage may

result in property damage, even with the use of a drain pan piped

to a drain. However, unanticipated damage can be reduced or

prevented by a leak detector or water shut-off device used in

conjunction with a piped drain pan. These devices are available

from some plumbing supply wholesalers and retailers, and detect

and react to leakage in various ways:

• Sensors mounted in the drain pan that trigger an alarm or turn

off the incoming water to the water heater when leakage is

detected.

• Sensors mounted in the drain pan that turn off the water supply

to the entire home when water is detected in the drain pan.

• Water supply shut-off devices that activate based on the water

pressure differential between the cold water and hot water

pipes connected to the water heater.

• Devices that will turn off the gas supply to a gas water heater

while at the same time shutting off its water supply.

WHEN SUCH LOCATIONS CANNOT BE AVOIDED, A SUITABLE

DRAIN PAN SHOULD BE INSTALLED UNDER THE HEATER.

Such pans should be fabricated with sides at least 2” (5 cm) deep,

with length and width at least 2” (5 cm) greater than the diameter

of the heater and must be piped to an adequate drain. The pan

must not restrict combustion air flow.

For appliance installation locations with elevations above 2000

feet (610 m), refer to HIGH ALTITUDE INSTALLATIONS section

of this manual for input reduction procedure.

LEVELING

If the unit is not level, insert the bolts which were used in crating

into the legs to correct this condition.

CLEARANCES

These heaters are approved for installation on combustible

flooring in an alcove when the minimum clearance from any

combustion construction are followed as indicated in figure 6

and Table 2.

The following units are approved for installation with side, rear

and ceiling clearances as indicated below:

The National Sanitation Foundation also recommends circulation

of 180°F (82°C) water. Where this is done, the circulation

should be very gentle so that it does not cause any unnecessary

turbulence inside the water heater. The circulation should be just

enough to provide 180°F (82°C) water at the point of take-off to

the dishwashing machine. Adjust flow by means of the plug cock

in the circulating line.

INSTALLATION INSTRUCTIONS

REQUIRED ABILITY

INSTALLATION OR SERVICE OF THIS WATER HEATER

REQUIRES ABILITY EQUIVALENT TO THAT OF A LICENSED

TRADESMAN IN THE FIELD INVOLVED. PLUMBING, AIR

SUPPLY, VENTING, GAS SUPPLY AND ELECTRICAL WORK

ARE REQUIRED.

WARNING

FAILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT

IN SERIOUS PERSONAL INJURY OR DEATH.

UNCRATING

The heater is shipped with the flue damper already installed. The

wiring conduit runs from the thermostat to the damper drive cover.

Before turning unit on, check to make sure the wiring conduit is

securely plugged into damper drive.

LOCATING THE HEATER

When installing the heater, consideration must be given to

proper location. Location selected should be as close to the

stack or chimney as practicable, with adequate air supply and as

centralized with the piping system as possible.

WARNING

THERE IS A RISK IN USING FUEL BURNING APPLIANCES

SUCH AS GAS WATER HEATERS IN ROOMS, GARAGES OR

OTHER AREAS WHERE GASOLINE, OTHER FLAMMABLE

LIQUIDS OR ENGINE DRIVEN EQUIPMENT OR VEHICLES ARE

STORED, OPERATED OR REPAIRED. FLAMMABLE VAPORS

ARE HEAVY AND TRAVEL ALONG THE FLOOR AND MAY BE

IGNITED BY THE HEATER’S PILOT OR MAIN BURNER FLAMES

CAUSING FIRE OR EXPLOSION. SOME LOCAL CODES

PERMIT OPERATION OF GAS APPLIANCES IN SUCH AREAS

IF THEY ARE INSTALLED 18” (.50 m). OR MORE ABOVE THE

FLOOR. THIS MAY REDUCE THE RISK IF LOCATION IN SUCH

AN AREA

CANNOT BE AVOIDED.

DO NOT INSTALL THIS WATER HEATER DIRECTLY ON A

CARPETED FLOOR. A FIRE HAZARD MAY RESULT.

Instead the

water heater must be placed on a metal or wood panel extending

beyond the full width and depth by at least 3 inches (7.6 cm) in

any direction. If the heater is installed in a carpeted alcove, the

entire floor shall be covered by the panel. Also, see the DRAIN

REQUIREMENTS.

THE HEATER SHALL BE LOCATED OR PROTECTED SO IT IS NOT

SUBJECT TO PHYSICAL DAMAGE BY A MOVING VEHICLE.

WARNING

FLAMMABLE ITEMS, PRESSURIZED CONTAINERS OR ANY

OTHER POTENTIAL FIRE HAZARDOUS ARTICLES MUST

CREATED BY NEEVIA DOCUSTAMP TRIAL VERSION (WWW.NEEVIA.COM)

CREATED BY NEEVIA DOCUSTAMP TRIAL VERSION (WWW.NEEVIA.COM)

This manual is related to the following products: