Venting system, Remote storage tank temperature control, Relief valve – John Wood Commercial Atmospheric Vent - AJWSM User Manual
Page 28: Hot water odor, Anode rod inspection
28
VENTING SYSTEM
Examine the venting system every six months for obstructions
and/or deterioration of the vent piping.
Remove all soot or other obstructions from chimney which will
retard free draft.
REMOTE STORAGE TANK
TEMPERATURE CONTROL
The water temperature in the storage tank (if used) is controlled
by the storage tank temperature control. The sensing element is
mounted in the hot water storage tank, see page 16.
A change in water temperature in the storage tank lower than
the tank temperature control setting will cause the sensor to
activate the circulating pump. The pump then circulates the water
through the heater where the thermostat senses the drop in water
temperature and activates main burner operation of the appliance.
If the storage tank temperature control is out of calibration, replace
with new control.
WARNING
SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL
TO SHUT OFF, TURN OFF THE MANUAL GAS CONTROL VALVE
TO THE APPLIANCE.
RELIEF VALVE
Periodically, the temperature and pressure relief valve should be
checked to ensure that it is in operating condition. Lift the lever
at the top of the valve several times until the valve seats properly
and operates freely.
If the appliance installation includes other relief valves, such as
in “remote” storage tanks etc., check their relief valve operation
with the same frequency.
WARNING
THE WATER PASSING OUT OF THE VALVE DURING THIS
CHECKING OPERATION MAY BE EXTREMELY HOT. AVOID
CONTACT AND DISCHARGE SAFELY TO PREVENT WATER
DAMAGE.
If the temperature and pressure relief valve on the heater
discharges periodically or continuously, a problem exists. This
may be due to unusually high water temperatures or pressures
in the system, or to a faulty relief valve. Contact your dealer or a
qualified service technician to find the cause of the problem and to
correct it. This may also be due to thermal expansion in a closed
water supply system. Contact the water supplier or local plumbing
inspector on how to correct this situation.
DO NOT PLUG THE
TEMPERATURE AND PRESSURE RELIEF VALVE.
WARNING
SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL
TO SHUT OFF, TURN OFF THE MANUAL GAS CONTROL VALVE
TO THE APPLIANCE.
HOT WATER ODOR
On occasion, hot water may develop a strong odor. If this occurs
drain the heater completely, flush thoroughly, and refill. If the
problem persists, chlorination of the heater and replacement of
the factory installed magnesium anodes with aluminum anodes
may correct the condition.
Occasionally water softener companies recommend removal of
heater anodes for odor reasons.
CAUTION
Unauthorized removal of the anode(s) will void the warranty. For
further information contact your dealer.
ANODE ROD INSPECTION
The heater tank is equipped with anode rods to provide corrosion
control. At least once a year the anode rods should be checked
to determine if replacement is necessary. Initially the anode rods
are approximately 7/8” (22mm) in diameter with a 1/8” (3mm)
diameter steel core wire running down the center of the anode
material. THE ANODES SHOULD BE REPLACED when the 1/8”
(3mm) diameter core wire is visible as this means that the anode
material has been expended in the control of corrosion.
For models with top inlet and outlet, it is recommended that, before
removing the inner cover for cleaning, inspection or removal of
inner parts, you obtain two new nipple collars, part no. 074060-000.
The nipple collars on the heater will usually be damaged when
removed. New pipe collars will insure that the seal is such as to
prevent leakage of flue products when properly installed.
NOTE: Anode rod inspection may need to be made more
frequently in areas subject to acid rain that obtains their
water supply from surface water as the low pH will accelerate
anode consumption.
CAUTION: Close cold water inlet valve serving heater
and open nearby hot water faucet to relieve the pressure
in the heater before attempting to remove anode(s) for
inspection.
RECOMMENDED PROCEDURE FOR
PERIODIC REMOVAL OF LIME DEPOSITS
FROM TANK TYPE COMMERCIAL WATER
HEATERS
The amount of calcium carbonate (lime) released from water is
in direct proportion to water temperature and usage, see chart.
The higher the water temperature or water usage, the more lime
deposits are dropped out of the water. This is the lime scale which
forms in pipes, heaters and on cooking utensils.
Lime accumulation not only reduces the life of the equipment
but also reduces efficiency of the heater and increases fuel
consumption.
The usage of water softening equipment greatly reduces
the hardness of the water. However, this equipment does
not always remove all of the hardness (lime). For this reason
it is recommended that a regular schedule for deliming be
maintained.
The time between cleaning will vary from weeks to months
depending upon water conditions and usage.
Refer to John Wood booklet, Form No. 4800, entitled “Why?
When and How” for detailed description on tank inspection and