How Do I?
143
§ N61:1 set to 0 for Interchangeable Pumps (Interchange Groups screen).
§ T25:30 set to 15 to 20 seconds for Combo Overlap Time (Timer Access screen). This allows
pump 1 to switch to XL (across-the-line) and run for that length of time while the VFD for
Pump 2 ramps up. This is a tuned value to ensure minimal pressure drop during the switch.
§ N7:148 set to 3 for Jockey cycle "Jump to 0" combo to allow shutdown sequence to work
(More N7 Regs Misc. Control).
§ B3:2/4 set to 1 for Jockey Cycle On (More N7 Regs Misc. Control).
§ N7:149 set to 3 for the Combo Limit for HSS (More N7 Regs Misc. Control).
· B60:05 enables or disables a PM pump.
· Optionally, press the Main Menu touch key to return to the Main Menu. (See also,
Main Menu
.)
· Optionally, press Back to return to the previous screen
· Press the down arrow (▼) in the bottom right corner of the screen to display page 2 of the
B60 register.
· B60:08 defines an Auto Lake Screen. If this object is enabled, you will need to review your ALS
settings on the
Auto Lake Screen
,
Lake Fill
, and
Filter screens
.
· B60:10 and B60:11 enable and disable filters. Again, you will need to review your filter settings on
the "Auto Lake Screen, Lake Fill, and Filter" screens.
· B60:12 allows lake fill. Again, you will need to review your filter settings on the "Auto Lake Screen,
Lake Fill, and Filter" screens.
· B60:16 allows a Water Feature / Timed Pump. If this is enabled, you will need to review your
Timed Pump Data
screen.
· Optionally, press the Main Menu touch key to return to the Main Menu. (See also,