14 define my start / stop features – Xylem 19 001 300 R2 Silent Storm VFD Pumping System OMRON Touch Screen Display Manual User Manual
Page 102

© 2013 Flowtronex
98
Omron Touch-Screen Display
· Optionally, press the down arrow (▼) to advance the next Calibration screen.
· See also,
Calibration Procedure with a Signal Generator
.
2.13.5.4 Calibrating Multiple Zone Pulse Flow Sensors
The calibration procedure for calibrating multiple one pulse flow sensors connected to an analog
transmitter is identical to the single zone procedure with the exception that zone 1 is now on channel 5
instead of channel 2, zone 2 is on channel 6, and zone 3 is on channel 7 (if applicable). No further
calibration is required. Channel 2 will display the total flow for all zones. Duplicate the single zone
calibration procedure from earlier in this section, but ensure that you use the correct channel.
· Tap the value next to any of these registers to open the calculator/keypad. Enter or edit the value.
(See also,
Calculator/Keypad
.)
· Optionally, press the Main Menu touch key to return to the Main Menu. (See also,
Main Menu
.)
· Optionally, press Back to return to the previous screen.
· Optionally, press the down arrow (▼) to advance the next Calibration screen.
· See also,
Calibration Procedure with a Signal Generator
.
2.14 Define My Start / Stop Features
You can access the Start/Stop Features screen and define your primary pumps start/stop
characteristic under normal conditions and when using VFD Bypass by pressing the Register Access
touch key on the
Main Menu
and opening the Register Access screen.