Generation II – Centripro 3-wire motors – recommended motor lead lengths
Based on Service Factor Amps, 30º C Ambient and 5% Voltage Drop
motor rating
60º C and 75º C Insulation - awG Copper wire Size
hp
Volts
kw
fla
Sfa
14
12
10
8
6
4
2
1/0
2/0
3/0
4/0
0.5
115
0.37
8.8
10.9
101
160
255
404
629
1002
1591
2530
3192
4029
5076
0.5
230
0.37
5.3
6.1
359
571
912
1444
2246
3581
5685
9040
-
-
-
0.75
0.55
6.6
7.8
281
447
713
1129
1757
2800
4446
7070
8920
-
-
1.0
0.75
8.1
9.4
233
371
592
937
1458
2324
3689
5867
7402
-
-
1.5
1.1
9.1
10.9
201
320
510
808
1257
2004
3182
5059
6383
-
-
2.0
1.5
9.9
12.2
180
286
456
722
1123
1790
2843
4520
5703
-
-
3.0
2.2
14.3
16.5
133
211
337
534
830
1324
2102
3342
4217
5323
-
5.0
3.7
24
27
-
-
206
326
507
809
1284
2042
2577
3253
-
3-wIrE, SINGlE phaSE 4" motorS - ElECtrICal Data, 60 hErtz, 3450 rpm
Generation II
– released for sale in february/march 2012
full load
Service factor locked
rotor
amps
winding
resistance
required
Control box
1
type
order
No.
rJ ref.
#
hp kw Volts Sf
amps watts amps watts
main
(b-y)
Start
(r-y)
3-
Wire
with
Q.D.
Cap.
Start
Box
M05411 50C301 0.5 0.37 115
1.6
Y – 8.8
B – 8.8
R – 0
675
Y – 10.9
B – 10.9
R – 0
980
44
1.0 -
1.4
2.5 -
3.1
CB05411
M05412 50C311 0.5 0.37
230
1.6
Y – 5.3
B – 5.3
R – 0
740
Y – 6.1
B – 6.1
R – 0
1050
21
5.1 -
6.1
12.4 -
13.7
CB05412
M07412 75C311 0.75 0.55
1.5
Y – 6.6
B – 6.6
R – 0
970
Y – 7.8
B – 7.8
R – 0
1350
32
2.6 -
3.3
10.4 -
11.7
CB07412
M10412 100C311 1.0 0.75
1.4
Y – 8.1
B – 8.1
R – 0
1215
Y – 9.4
B – 9.4
R – 0
1620
41
2.0 -
2.6
9.3 -
10.4
CB10412
3-
Wire
with
CSCR
(CR)
or
Mag-
netic
Con-
tactor
(MC)
Con-
trol
Box
M05412 50C311 0.5 0.37
1.6
Y – 4.2
B – 4.1
R – 1.8
715
Y – 4.8
B – 4.3
R – 1.8
960
21
5.1 -
6.1
12.4 -
13.7
CB05412CR
M07412 75C311 0.75 0.55
1.5
Y – 4.8
B – 4.4
R – 2.5
940
Y – 6.0
B – 4.9
R – 2.3
1270
32
2.6 -
3.3
10.4 -
11.7
CB07412CR
M10412 100C311 1.0 0.75
1.4
Y – 6.1
B – 5.2
R – 2.7
1165
Y – 7.3
B – 5.8
R – 2.6
1540
41
2.0 -
2.6
9.3 -
10.4
CB10412CR
M15412 150C311 1.5
1.1
1.3
Y – 9.1
B – 8.2
R – 1.2
1660
Y – 10.9
B – 9.4
R – 1.1
2130
49
2.1 -
2.5
10.0 -
10.8
CB15412CR or
CB15412MC
M20412 200C311
2
1.5
1.25
Y – 9.9
B – 9.1
R – 2.6
2170
Y – 12.2
B – 11.7
R – 2.6
2660
49
1.6 -
2.2
4.8 -
5.9
2
CB20412CR or
CB20412MC
M30412 300C311
3
2.2
1.15
Y – 14.3
B – 12.0
R – 5.7
3170
Y – 16.5
B – 13.9
R – 5.6
3620
76
1.0 -
1.4
2.0 -
2.5
CB30412CR or
CB30412MC
M50412 500C311
5
3.7
1.15
Y – 24.0
B – 19.1
R – 10.2
5300
Y – 27.0
B – 22.0
R – 10.0
6030
101
.6 - .8
1.3 -
1.7
CB50412CR or
CB50412MC
¹ A CSCR control box with a CR suffix can be replaced by a Magnetic Contactor model ending in MC.
2
Prior to November 2012, the Winding Resistance was 10.8 – 12.0.
GENEratIoN II – 3-wIrE, 4" SINGlE phaSE rECommENDED wIrE lENGthS