GE Industrial Solutions Mini-BDFB User Manual
Page 11

Micro-BDCBB ED83368-30
850027449 Issue 1 DRAFT December 2012
11
Load Overload
Delay
An Overload Delay can be set to prevent nuisance alarms. This delay is
configurable between 0-300 seconds. Factory default is 0 seconds.
Assigned Circuits
The VIM1 has eight individual load circuits with each circuit having voltage and
shunt measurement capability. These circuits are pre-wired with fixed positions
in the Lineage BDFB/BDCBBs. If circuit wiring from the VIM is redressed in the
field this feature can be used to assign the appropriate circuit to the new load
location.
Note: in the 6-load H569-445 circuits 1-6 are attached in a descending order
viewing from the front of the system in a top left to right numbering scheme. The
VIM1 will automatically assign the right circuit if only the first “Load Location” is
utilized and the internal wiring is not touched. Note: if wiring has been
rearranged details of the circuit connections can be seen in T83150-30.
Control and
Operations
Parameters
Description
Start Lamp Test
Cycles the illumination of the front panel LED and Backlight through Red, Amber,
and Green
Clear Latched
Events
Clears a latched Overload Alarm event. Note the Overload Latched Event must be
enabled to have a latched alarm.
Start Alarm Test
Asserts Form-C alarms available at connector J3 in a fixed sequence: Fuse Alarm
(FA), Power Loss (PL), and Overload (OVL). Alarm asserted is displayed on the front
panel. Feature can be used to test the site’s remote monitoring systems and
wiring.
Bullet Style Load Circuit Breakers
Ordering Code
Amperage
CB Positions (Poles)
Min. Wire Gage
407998137
3
1
10
407998145
5
1
10
407998152
10
1
10
407998160
15
1
10
407998178
16
1
10
407998186
20
1
10
407998194
25
1
10
407998202
30
1
10
408213486
40
1
8
407998210
45
1
8
407998228
50
1
6
407998236
60
1
6
407998244
70
1
2
407998251
80
1
2
407998269
90
1
2
407998277
100
1
2
CC848808551
100
2
2
408185353
125
2
2
408185346
150
2
1/0
408564941
200
3
2/0
408573975
225
3
4/0
408535752
250
3
4/0
Multi-Pole Adapter Bus Kits – 1 per multi-pole breaker
Ordering Code
CB Positions (Poles)
Hardware Included
850021775
2
5/16” on 1” centers
850021955
3
5/16” on 1” centers