9 specifications, Specifications – GE Industrial Solutions Digital Energy GT Series UPS 5_6_8_10 kVA User Manual
Page 41

9 SPECIFICATIONS
Model
:
GT5000 GT6000 GT8000 GT10000
Ratings
Power ratings depending on input voltage
:
VA / W
VA / W
VA / W
VA / W
100V / 200V
:
4000 / 3400
4800 / 3400
6400 / 6400
8000 / 6400
110V / 220V
:
4500 / 3800
5400 / 3800
7200 / 7200
9000 / 7200
115V / 230V
:
5000 / 4000
6000 / 4200
8000 / 8000
10000 / 8000
120V / 208V
:
4800 / 4200
5200 / 4200
8000 / 6900
8700 / 8000
120V / 240V
:
5000 / 4200
6000 / 4200
8000 / 8000
10000 / 8000
127V / 220V
:
4800 / 4200
5200 / 4200
8000 / 6900
8700 / 8000
Input thermal circuit breaker (A)
:
30
30
60
60
Internal input fuse 250V, slow (A)
:
30
30
30*2
30*2
Input converter
AC input voltage
:
Nominal: 120 / 208 V
AC input voltage range
: 100/(173-200), 110/(190-220), 115/(198-230), 120/(208-240), 127/(220) V
Input current waveform
:
sine wave
Input current (A) at nominal input voltage
:
20
20
40
40
Input power factor
:
> 0.97
Input frequency range
:
40 - 70 Hz
Input phase (L1 to L2)
:
120° / 180° / 240° ±10°
Inrush
current
:
40 40 40 40
Output converter
AC output voltage
:
100 / 110 / 115 / 120 / 127 V (selectable)
AC output voltage tolerance
:
L-N ± 3%; L1-L2 ± 5%
L-N ± 2%; L1-L2 ± 5%
Output frequency
:
50 / 60 Hz, auto selection
Output frequency range
:
nominal ± 5% with mains synchronizing
Output waveform
:
sine wave
Harmonic distortion
:
< 3% with linear load, < 5% with non-linear full load
Power factor at nominal input voltage
:
0.87
0.8
0.86
0.92
Crest factor (peak to RMS current)
:
≤ 3 : 1
Capacity appliance outlets
:
with 55A Terminal Block
Bypass
AC input voltage range
:
± 15% of selected output voltage
Frequency tracking rate
:
1Hz/s
Frequency tracking range
:
± 5% of selected frequency
Typical transfer time, msec
:
0
Overload capability
:
fully protected against overload and short circuits
Overload behavior during battery operation
:
130% during 10 seconds
130% during 1 minute
:
200% during 2 seconds
200% during 5 seconds
Overload behavior during bypass operation
: depends on rating of thermal circuit breaker
overload protection
125% of TCB value for 200 seconds
110% for 300 seconds
200% of TCB value for 10 seconds
130% for 30 seconds
300% of TCB value for 4 seconds
200% for 5 seconds
Batteries (ratings given for 25ºC)
Nominal voltage (Vdc)
:
144
144
288
288
Number / Ah batteries
(in battery kit and battery ext. pack)
:
12pcs / 8Ah
12pcs / 8Ah
24pcs / 8Ah
24pcs / 8Ah
Type :
REW45-12
FR
Service life
:
up to 5 years (depending on use)
Recharge current
:
1 A
Battery recharge time
(batt. discharged at 100% load)
:
6 hours for 90% capacity
3 hours for 90% capacity
Runtime in minutes
at typical load (75%)
:
8
8
9
9
25%
:
31 31 40 40
50%
:
14 14 16 16
75%
:
8 8 9 9
100%
:
5 5 5 5
General
Weight UPS kg
:
30.3 Kg (67 lbs)
49.3 Kg (109 lbs)
Dimensions UPS (h
x
w
x
d)
: 176x430x592 mm (6.9x16.9x22.55 in)
267x430x660 mm (10.5x16.9x26 in)
Weight battery pack kg
:
43 Kg (94.7 lbs)
91 Kg (200.4 lbs)
Dimensions battery pack
: 87x430x592 mm (3.47x16.9x2255 in)
173x430x660 mm (6.8x16.9x26 in)
Enclosure / protection
:
steel-plastic
/
IP20
Environment
Safety :
UL1778
Electromagnetic compatibility
:
EMI: FCC CFR47 Part 15, class A, ESD: IEC61000-4-2, level 4
RS: IEC61000-4-3, level 3, EFT: IEC61000-4-4, level 4, Surge: IEC61000-4-5, level 3
ANSI C62.41 (IEEE587) Category A (level 3) & B (level 1)
Ambient temperature
:
0 to +40ºC
Audible noise at 1 meter
:
< 55 dB(A), load and temperature dependent
Max. relative humidity
:
90% (non-condensing)
Color
:
Black - RAL 9005
modifications reserved
41