GE Industrial Solutions GT Series UPS programmable relay card User Manual
Programmable relay i/o card user manual, Presentation, Technical specification

PROGRAMMABLE RELAY I/O CARD
USER MANUAL
PRESENTATION
FEATURES 
This relay I/O card is an UPS management 
product with 6 relay output contacts for monitoring 
UPS status and 1 input contact as shutdown UPS 
or test battery command. 
Features: 
UPS status information presented as 6
contact closures and they are changable.
Programmable output contacts, monitors the
UPS events that users really concern in 
different practices. 
Customized normal open or normal close for
individual relay.
 Configurable UPS shutdown delay time. 
 Configurable input signal as shutdown UPS or 
battery test.
Has the ability to protect up to 6 computers
unattended shutdown gracefully.
TECHNICAL SPECIFICATION
TECHNICAL SPECIFICATION
Size
130 x 60 mm
Weight
200 g
Operating Temperature 0 ~ 40
° C
Operating Humidity
10 ~ 80 %
Power Input
8 ~ 20V DC
Power Consumption
1.2 Watts
 
OUTPUT CONTACT RATING 
Maximum
DC Voltage DC Current
Relay 
R1~R6 
24 V
1A
 
INPUT RATING 
Maximum
DC Voltage DC Current
Input
24 V
10 mA
APPLICATION EXAMPLE
In this case we’ll adopt the default settings, please 
keep SW1 and SW2 to OFF position. Provide less 
than 24VDC to Common contact and connect the 
lamps to R1~R6 terminals. Press the button over 
3 seconds to shutdown UPS remotely. 
Common
GND-R
R1
R2
R3
R4
R5
Input
+12V
Summary Alarm
Power Fail
Battery Low
On Bypass
Overload
Shutdown UPS
R6
Over Temperature
INTERNAL CIRCUIT
R1
R2
R3
R4
R5
Common
GND-R
Input
+5V
CPU Pin
R6
 
OUTLINE 
GND-R
Common
R1
R2
R3
R4
R5
R6
Input
Tx
Rx
GND-C
SW1
SW2
 
I/O PINOUT 
GND-R: Ground for relays 
Common: 12~24VDC 
 Default 
Alarm
Event
R1 Summary
Alarm
R2 Power
Fail
R3 Battery
Low
R4 On
Bypass
R5 Overload 
R6 Over 
Temperature
Input: Remote shutdown or battery test 
Tx: Transmit to PC, connect to sub9-pin2 
Rx: Receive from PC, connect to sub9-pin3 
GND-C: Ground for configuration Tx and Rx pins
 
OFF (Default) ON
SW1 Normal
open
for default settings
Normal close 
for default settings 
SW2 Default settings
Customized settings
PROGRAMMABLE CONTACTS
COMMUNICATION SETUP 
1. Connect 
Tx to pin2, Rx to pin3 and GND-C to
pin5 of PC RS232 port.
2. In Windows environment, launch Hyper-
Terminal application then open the specified 
COM port. 
3. Set the following properties: 
 Baud 
rate:
2400, Data Bits: 8, Parity: None
Stop
Bit:
1, Flow Control: None
 
CONFIGURATION 
1. Press 
Relay I/O card.
+---------------------------+
| UPS Relay Card |
+---------------------------+
Firmware Version: Relay Card V1.4
[1].Customize Output Relay
[2].Configure Input Signal
[3] Customize Normal Open or Normal Close
[0].Quit
Please Enter Your Choice =>
2. Press ‘1’ to configure the alarm event for
R1~R6. 
In this menu, contacts R1~R6 are allowed to 
assign to different power events. 
+
|
---------------------------+
 Customize Output Relay |
+---------------------------+
 Relay Selected Event
[1].Relay1: Summary Alarm
[2].Relay2: Power Fail
[3].Relay3: Battery Low
[4].Relay4: On Bypass
[5].Relay5: Overload
[6] Relay6: Over Temperature
[0].Back To Previous Menu
Please Enter Your Choice =>
After finishing the configuration please switch 
SW2 to ON position to apply your settings, 
switch SW2 back to OFF position to apply 
default settings. 
3. Press ‘2’ to configure the Input signal.
+---------------------------+
| Configure Input Signal |
+---------------------------+
[1].Act as Shutdown or Test: Shutdown
[2].Input Signal Confirm: 3 Seconds
[3].Delay Before Shutdown: 30 Seconds
[0].Back To Previous Menu
Please Enter Your Choice =>
In this menu, the input signal can be redefined 
as shutdown UPS or battery test signal. 
Meanwhile, the UPS shutdown delay time is 
also adjustable to maximum 9999 seconds. 
4. Press ‘3’ to configure the normal open or
normal close for each relay.
+---------------------------+
| Customize Output Relay |
+---------------------------+
 Relay Selected Event
[1].Relay1: Normal Close
[2].Relay2: Normal Open
[3].Relay3: Normal Close
[4].Relay4: Normal Open
[5
[6
].Relay5: Normal Close
].Relay6: Normal Open
[0].Back To Previous Menu
Please Enter Your Choice =>
Switch SW2 to ON position to apply your 
settings. If the SW2 is backed to OFF position 
to apply default settings then you can use 
SW1 to control normal open or normal close 
for all relays. 
5. Press ‘0’ to quit this configuration session.
The system would prompt you to save or not. 
Press ‘Y’ to save your settings, ‘N’ to ignore. 
POWER OPTION IN WIN 2000/XP
This relay card has the ability to provide UPS 
signals for Windows NT4/2000/XP/2003. Firstly 
please connect the RS232 port from your PC to 
the relay card shown as the following. 
Then open the power option from control panel 
and click on the UPS tab to setup the signals 
polarity, select Positive for Power Fail, Low 
Battery and UPS 
Shutdown. 
Because the 
R1~R6 contacts 
are programmable, 
we can configure 
the output 
contacts for 3 
computers with 2 
signals (power fail 
and low battery) or 
6 computers with 
one signal (power 
fail or low battery). 
 
Note: To ensure all of the protected computers 
have the same ground level, it is required to 
connect their input power to the same UPS. 
Common
GND-R
R1
R2
R3
R4
R5
Input
Power Fail
R6
Battery Low
RTS pin7
GND pin5
CTS pin8
DCD pin1
DTR pin4
Shutdown UPS