GE Industrial Solutions Spectra Series Power Panelboards AFP Filler Plates User Manual
Spectra series™ power panelboards, Installing the filler plates, Type afp filler plates
![background image](/manuals/295586/1/background.png)
g
Spectra Series™ Power Panelboards
Type AFP Filler Plates
WARNING:
Danger of electrical shock or injury.
Turn
OFF power ahead of the panelboard or
switchboard before working inside the
equipment or removing any component
.
Do
not remove circuit protective devices or any
other component until the power is turned
OFF.
Installing the Filler Plates
Use the following procedure to install type AFP filler
plates. The catalog numbers covered by this instruction
are listed in Table 1.
Catalog
Number Use with ADS Switch
Box
Width, in.
AFP10T 400 A & 600 A J or T fuse, 10X main
or branch
36, 44
AFP10X 400 A & 600 A R fuse, 10 X main or
branch
44
AFP19X 800 A & 1200 A, 19X main or branch
44
AFP4X
30 A & 60 A, 4X
44
AFP5X
60 A & 100 A, 5X
44
AFP7T
100 A & 200 A T fuse, 7X
44
AFP7X2 200 A R fuse, 7X double branch
44
AFP7X
200 A R fuse, 7X main or single
branch
36, 44
Table 1. Type AFP filler plates covered by this instruction.
1.
For ease of assembly, the filler plates should be
installed after the side trim is in place.
2.
Insert the flat end of the filler plate into the channel
on the edge of the side trim, as shown in Figure 1.
Figure 1. Inserting the filler plate into the side trim.
3.
Attach the opposite end of the filler plate to the
flange on the device, using the screws furnished on
the filler plate, as shown in Figure 2. Tighten the
screws to 25–30 in-lb.
Figure 2. Attaching the filler plate to the device.
g
GE Industrial Systems
General Electric Company
41 Woodford Ave., Plainville, CT 06062
GEH5590 R03 0701
© 2001 General Electric Company
These instructions do not cover all details or variations in equipment nor do they provide for every possible contingency that
may be met in connection with installation, operation, or maintenance. Should further information be desired or should
particular problems arise that are not covered sufficiently for the purchaser’s purposes, the matter should be referred to the
GE Company.
GEH5590 Installation Instructions
R03
Side Trim
Filler Plate
Screw