Technical specifications – GE Industrial Solutions EP0300AC48TEZ User Manual
Page 2

GE Critical Power reserves the right to make changes to the product (s) or information contained herein without notice. No liability is assumed as a result of their use or
application. No rights under any patent accompany the sale of any such product(s) or information.
©
2013
GE Critical Power (Bangalore, India) All Rights Reserved.
Document Rev No: R0.1 Date: 5
th
February 2013
PDF name: EP0300AC48TEZ PDS.pdf
Technical Specifications
Input Parameters
Operating Voltage range
90-290 Vac
Disconnect: < 90Vac & > 290Vac
No damage up to 300Vac
Full Power input voltage
Range
90-290 Vac
Frequency
45 to 65Hz
Maximum Current
4A (rms) 230Vac,100% load
Power Factor
> 0.99 at 230Vac,100% load
Total Current Harmonic
Distortion (THD)
< 10% at 230Vac,100% load
Efficiency
≥ 90%. 230Vac,100% load
Input protection
In built surge protection (2kV/3kA)
Inline
fuse
Output Parameters
Voltage, nominal
48 Vdc
Voltage adjust range
42 … 57 Vdc (controller)
Rated output Power
300W
Output Current @...V
5.5A@54V
Maximum current
6.25A
Static Voltage regulation
±1% from 10% to 100% load
Noise (Ripple + spikes)
≤ 100 mV
rms
Load sharing
10%
I/P and O/P connector
Rear side
Output protection
Over voltage shutdown
Blocking diode
Short circuit proof
Over temperature protection
Note:
As a result of continuous product improvement, all specifications are subject to change without prior notice. All performance parameters are valid at Nominal input (230Vac) and nominal output
(48Vdc) conditions unless otherwise specified.
Applicable Standards
Electrical safety
IEC 60950-1
UL
60950-1
CSA
22.2
EMI
As
per
CISPR-22
EMC
IEC 61000-4-5, (Surge immunity limits)
IEC 61000-4-6, (RF Conducted susceptibility immunity limits)
IEC 61000-4-3, (Radiated Electromagnetic Field immunity limits)
IEC 61000-4-4, (EFT/ Burst immunity limits)
IEC 61000-4-2, (ESD Immunity limits)
Harmonics
EN 61000-3-2
Environment
RoHS compliant
Ordering Information
Product Description
Comcode
EP0300AC48TEZ
48V, 300W rectifier
150022411
Country of Sale
South Asia
India
SE Asia
-
NA -
CALA
-
European
-
Other Parameters
Isolation
3.0 kVac – I/P & O/P
1.5 kVac – input & earth
0.5 kVac – output & earth
Visual Indications
Normal LED (Green):
3 status (Blink, OFF, ON)
Fault LED (Red):
3 status (Blink, OFF, ON)
Operating temp
-25°C to +75°C
Power De-rating
+60°C to +75°C
Operating Humidity
5% to 95% RH non-condensing
MTBF
> 150k hours Telcordia SR-332,
Method 1, Case 3 (Ambient
Temperature.: 25°C)
Audible Noise
< 60dBA at an ambient noise level of
45dBA, and at ambient temperature
of 25°C
Mechanical
Width
50.4 mm (2”)
Height 45
mm
(1.75”)
Depth 228.6mm
(9”)
Weight
0.5 kg (1.1 lbs)