beautypg.com

GE Industrial Solutions Remote Racking Operator: Low Voltage AKR Circuit Breakers User Manual

Page 12

background image

Remote Racking Operator for AKR Breakers

12

4-3 Field Modification to existing Breaker doors.

All existing small and large frame AKR Breaker
doors can be modified in the field to
accommodate the new AKR remote racking

operator. A drilling template kit (CAT#
AKREGDRTEMP) can be provided with (5) drilling
templates (one for each type of breaker door).
The racking flag assemblies (CAT#
AKREGDRMOD) can also be ordered for each

modified breaker door.

Below is a picture demonstrating how to locate
and drill holes in an existing 30S, 75/100 or 125
breaker door. A picture demonstrating how to

locate and drill the holes for a 30/50 breaker
door is located on the next page.


Refer to page 14 for remote racking flag details.




1. Insert bushing of template into

the existing racking hole.

2. Align inside edge of template
with outer edge of door.

3. Drill (1) 1.75” diameter

hole through the door.

4. Drill (1) 0.251”
diameter hole

through the door.

Figure 7

Door drilling template for AKR 30S, 75/100 and 125 doors

Existing breaker compartment door.