Step 6, Troubleshooting:
Ensure that breaker is installed correctly and all
terminal connections are torqued per
instructions.
If the breaker fails to close, check:
1. For overloads and short circuit on the system.
2. Handle position - TRIPPED - reset by moving
handle fully to OFF position and then to the
ON position, see figure 6.
3. Under voltage trip is supplied with rated
voltage.
4. Shunt trip is de-energized and no trip signal
exists.
5. Breaker trip unit settings are properly
adjusted.
If technical assistance is required, contact your
local sales office. In the US call GE Post Sales
Customer Service, 1 888 437 3765.
Step 7, Maintenance:
Generally, no maintenance is required but it is
recommended that the breaker be cleaned and
inspected on an annual basis.
Warning: Danger of electrical shock or injury.
Turn off power supplies ahead of equipment
before attempting to service or accessories.
Important: Danger d’electrocution. Couper
l’alimenation avant d’effectuer toute action
d’entretien.
Operate the breaker push to test button and
toggle the handle several times, testing the
mechanical operation of the device. If there are
any signs of damage or if the mechanism is
sluggish or sticky, replace the breaker.
For abnormal or heavy duty conditions refer to
NEMA publication AB4 and recommended
practices of NFPA70B.
Step 8, Storage:
Store in a dry, dust free, environment protected
from corrosion. Long-term storage should be in
the original shipping carton. Temperature range
–40
o
C to +40
o
C.
Step 9, Accessories:
For full details of the accessories and their
application, contact your local GE
representatives. When installing accessories
read the accompanying accessory installation
instruction and follow carefully all cautions and
warnings.
These instructions do not cover all details or variations in equipment nor do they provide for
every possible contingency that may be met in connection with installation, operation, or
maintenance. Should further information be desired or should particular problems arise that are
not covered sufficiently for the purchaser’s purposes, the matter should be referred to the GE
Company. The circuit breaker is a sealed unit, which contains no user serviceable parts.
Tampering with seal will void warrant.
g
GE Consumer & Industrial
41 Woodford Avenue
Plainville, CT USA 06062
www.geconsumerandindustrial.com
DEH40360 05 R0833843 © 2004 General Electric Company
Outer 2 positions
Right pocket auxiliary
Switch ID
Figure 7, Typical accessories.
See buylog
®
for details
Outer 2 positions
Left pocket auxiliary
Switch ID
Inner Position Left pocket
shunt-trip/under voltage
Trip Bell-alarm ID
Apply Accessory Label to
side of breaker
Shunt trip/Under
Voltage Module