Power Break® II Devices
Draw-Out Device Installation
5
Removing the Device
Use the following procedure to remove the draw-out
device from the substructure.
CAUTION: The device must be
OFF
before it is dis-
connected and removed.
ATTENTION: Le mécanisme doit être à OFF avant qu’il
ne soit débroché et déposé.
1. Engage the
1 2
-inch square end of the racking
shaft with the supplied wrench, catalog number
TDORT, as illustrated in Figure 7, and rotate the
shaft counter-clockwise to withdraw the device to the
TEST
or
DISCONNECTED
position. The compartment
position indicator is shown in Figure 8.
2. Pull the substructure rails out as far as possible until
they drop into the horizontal locked position, as
illustrated in Figure 9.
3. From the
DISCONNECTED
position, pull the device
out on the rails until the front rollers fall into the
detent, as illustrated in Figure 6.
4. The device can now be rotated about the front roller
by pulling forward, as illustrated in Figure 10, for
inspection of the rear of the device, or it can be
completely removed after attaching the Lifting Bar,
as illustrated in Figures 4 and 5.
Figure 9. Withdrawing the substructure rails.