GE Industrial Solutions Voltage Conditioner Plate SVCA600D User Manual
Voltage conditioner plate, Geh-6252 installation instructions, Ge energy industrial solutions

Overview
The General Electric Voltage Conditioner Plate is used
to provide voltage-sensing signals to Spectra
®
RMS
Molded-Case Circuit Breakers with microEntelliGuard
TM
or MicroVersaTrip
®
PM/Plus Trip Units via the Distribution
Cable System. The Voltage Conditioner Plate includes
the Voltage Conditioner Assembly (catalog number
SVCAA) as an integral component and also includes fuse
protection for the AC source input terminals and three
1-VA @ 60 Hz high accuracy potential transformers. The
plate has the maximum capacity to provide voltage-
sensing signals to a Distribution Cable System consisting
of 20 Spectra
®
RMS Molded-Case Circuit Breakers with
microEntelliGuard
TM
or MicroVersaTrip
®
PM/Plus Trip Units
with a maximum system cable length of 40 feet.
The Voltage Conditioner Plate requires a power supply
source of +24Vdc to operate properly. The Power
Supply Assembly (catalog number SPSAA) or Power
Supply Plate (catalog number SPSA120, SPSA208,
SPSA240, SPSA480 or SPSA600) can provide this
required input. The unit also requires direct AC voltage
inputs from the AC source (ratings of 120Vac, 208Vac,
240Vac, 277Vac, 480Vac or 600Vac are available). The
Voltage Conditioner Plate is designed to operate in
temperatures between 0°C and 70°C.
GEH-6252 Installation Instructions
Voltage Conditioner Plate
For Spectra
®
RMS Molded-Case Circuit Breakers
with microEntelliGuard
TM
, MicroVersaTrip
®
PM or MicroVersaTrip
®
Plus Trip Units
For Catalog Numbers SVCA120Y, SVCA208Y. SVCA240Y, SVCA277Y, SVCA480Y,
SVCA480D, SVCA600D
Circuit Breaker Accessory
GE Energy
Industrial Solutions