GE Industrial Solutions Spectra Series Power Panelboards APM2404PQM, APM2403PQM, and APM2084PQM User Manual
Spectra series™ power panelboards, Application, Installation
g
Spectra Series™ Power Panelboards
Neutral and Ground Wire Kit for PQM Panel Metering
Catalog Number
APMNEUGNDWK
Application
For use with meter modules type APM6004PQM,
APM6003PQM,
APM4804PQM,
APM4803PQM,
APM2404PQM, APM2403PQM, and APM2084PQM.
Installation
WARNING:
Danger of electrical shock or injury.
Turn
OFF power ahead of the panelboard or
switchboard before working inside the
equipment or removing any component
.
Equipment is to be installed and maintained by
properly trained and qualified personnel only.
In the following instructions and figures, numbers in
brackets refer to the items in Table 1.
1. Confirm the contents of the kit.
This kit is for
installing the ground wire and neutral wire (if neutral
is required).
The kit contains parts for making the neutral
connection (if the meter module is provided with
one) and ground connection on PQM Panel
Metering. The 12-gauge wire is used for the ground
connection and thus is always used. If a neutral is not
required, then discard the 14-gauge wire. Figure 1
shows all the parts included in this kit, which are
listed in Table 1.
2. Locate the terminal board in the meter module.
After
installation of the panel, ground, and neutral (if
required) into the enclosure, locate the module in the
panel interior. Open the door of the module and
locate the 12-point terminal board, as shown in Figure
2.
3. Installing the ground and neutral wire.
Locate the
terminals marked GND 6 and VN (if required), as
shown in Figure 3. Loosen the slotted screws on the
right side of the terminal board. Insert one end of the
12-gauge wire [1] into the GND 6 slot. Insert one end
of the 14-gauge wire [2] into the VN slot. Tighten the
screws to 12 in-lb.
[1]
[2]
[3]
[4]
Figure 1. Parts Included In the neutral and/or ground wire kit, catalog
number APMNEUGNDWK.
Item Description
Part #
Qty.
1
12-gauge black wire
273A7900P12BK19
8 ft.
2
14-gauge black wire
273A7900P14BK19
8 ft.
3
Tie wraps
PEL#PLT1.5I-M
16
4
Saddles
331A2242P1
8
Table 1. Parts list for kit APMNEUGNDWK.
Figure 2. Location of the 12-point terminal board in the meter
module.
DEH40394 Installation Instructions
R02
Terminal Board