7. Assemble remaining terminal assemblies similarly
on all poles so as to populate as 3pole / 4 pole
breaker.
8. The bus bars to be supported within 200mm
distance and tightened to 80Nm (59 ft-lbs) torque.
Top Heat sink LH
(with clearance hole)
Top Heat sink RH
(with tapping)
M8, Mtg
hardware
Top Spacer
Bottom Heat sink RH
(with tapping)
Bottom Heat sink LH
(with clearance hole)
Bottom Spacer
Top Heat sink LH
(with clearance hole)
Top Heat sink RH
(with tapping)
M8, Mtg
hardware
Top Spacer
Bottom Heat sink RH
(with tapping)
Bottom Heat sink LH
(with clearance hole)
Bottom Spacer
M12 Mtg
hardwares
Top terminal
assembly
Bottom terminal
assembly
M12 Mtg
hardwares
Top terminal
assembly
Bottom terminal
assembly
Fig B. Heat sink Asm with spacers (Middle pole)
For 3200A , (ANSI) 3 pole, fixed type
Fig
C.
Outer pole, Back Connected Terminations
asm For 3200 A, (ANSI) 3 Pole, fixed type
Top Heat sink (RH)
(with clearance hole)
M8, Mtg
hardware
M8, Nuts
Top Spacer
Top Heat sink (RH)
(with clearance hole)
M8, Mtg
hardware
M8, Nuts
Top Spacer
Fig
D.
Outer pole Heat Sink with spacer assembly
For 3200 Amperes (ANSI), 3 Pole, Fixed type