with M8 mounting hardware’s to 16 Nm (11.8 ft-
lbs) torque.
7. Assemble remaining terminal assemblies similarly
on all poles so as to populate as 3pole / 4 pole
breaker.
8. The bus bars to be supported within 200mm
distance and tightened to 80Nm (59 ft-lbs) torque.
Top Spacer
Bottom Spacer
Top Heat Sink RH
(With tapping)
Top Heat Sink LH
(With clerance hole)
Bottom Heat Sink RH
(With tapping)
Bottom Heat Sink LH
(With clerance hole)
M8 Harware
Top Spacer
Bottom Spacer
Top Heat Sink RH
(With tapping)
Top Heat Sink LH
(With clerance hole)
Bottom Heat Sink RH
(With tapping)
Bottom Heat Sink LH
(With clerance hole)
M8 Harware
M10 Hardware
40 Nm torque
M10
Spring washer
M10 plain
Washer
M10 Hardware
40 Nm torque
M10
Spring washer
M10 plain
Washer
M10
Spring washer
M10 plain
Washer
Fig B. Heat sink Asm with spacers (Middle pole)
for 3200 Amperes (ANSI) 3 pole
Fig C. Outer pole Back Connected Terminations
assembly for 3200 Amperes (ANSI) 3 Pole
M8, Nut
M8, Hardware
Top spacer
Bottom spacer
Heat sink
M8, Nut
M8, Hardware
Top spacer
Bottom spacer
Heat sink
Fig D. Outer pole Heat Sink with spacer assembly
for 3200 Amperes (ANSI), 3 Pole