GE Industrial Solutions AF-600 FP Field Installed Relay User Manual
Af-6 seriesdrives
AF-6 SeriesDrives
1
Relay Option OPCRLY
The OPCRLY option includes 3 pieces of change over contacts and can be f itted into option slot B.
Electrical Data:
Max. terminal load (AC) .............................................................................................................................. 240 V AC 2A
Max. terminal load (DC) ............................................................................................................................. 24 V DC 1A
Min.
terminal load (DC) ........................................................................................................................................... 5 V 10 mA
Max. switching rate at rated load/min load .............................................................................. 6 min
-1
/20 sec
-1
How to add the OPCRLY option:
Warning Dual supply
IMPORTANT
1. The label MUST be placed on the keypad frame as shown (UL approved).
- The power to the drive must be disconnected.
- The power to the livepart connections on relay terminals must be disconnected.
- Remove the keypad, the terminal cover and the cradle from AF-650 GP.
- Fit the OP CRLY option in slot B.
- Connect the control cables and relief the cables by the enclosed cable strips.
- Various systems must not be mixed.
- Fit the extended cradle and terminal cover.
- Replace the keypad.
- Connect power to the drive.
- Select the relay functions in par. E-24 [6-8], E-26 [6-8] and E-27 [6-8].
NB (Array [6] is relay 7, array [7] is relay 8, and array [8] is relay 9).