GE Industrial Solutions ASTAT BP User Manual
Page 12

ASTAT BP User Manual
12
GE Industrial Solutions
©2013 GE Company All Rights Reserved
Under Voltage:
Trips when main voltage drops below 50-90% of
Line Voltage, time delay 1-
10 Sec. Optional Auto Reset.
Over Voltage:
Trips when main voltage increase above 110-125% of
Line Voltage, time
delay 1-10 sec.
Phase Loss, Under/over
Frequency:
Trips when one or two phases are missing, or frequency is < 40Hz or > 65Hz.
Optional auto reset.
Phase Sequence:
Trips when phase sequence is wrong
Long Slow Speed Time:
Trips if operating at slow speed TRQ for more than 1-30 sec (1-250 sec
3
)
Wrong Connection:
Prevents starting, trips if motor is not connected / incorrectly connected to the
ASTAT-BP (not active in
D.Set: Generator Parameters)
Shorted SCR:
Trips if one or more SCRs have been shorted
(not active in
D.Set: Generator Parameters)
Heat Sink Over
Temperature:
Trips when heat-sink temperature rises above 85°C
External Fault:
Trips when an external contact closes for 2 sec.
Motor Thermistor:
Trip level setting 1-10K
Control:
Displays:
LCD in 4 – Field selectable languages and 8 LEDs
Keypad:
6 keys for easy setting
Aux Contact –
Programmable:
1 NO, 8A, 250VAC, 2000VA
Fault Contact:
1 NO, 8A, 250VAC, 2000VA
Communication:
RS 485 with Modbus protocol for full control and supervision
Communication (optional):
Profibus DPV1 for full control and supervision
Communication (optional):
DeviceNet
tm
for full control and supervision
Temperatures Operating:
-10° to 60°C; For ambient temperature between 50°C and 60°C, derate the
current by 2.5% for each °C that is above 50°C
Storage:
-20° to 70°C
Standards:
Dielectric Test:
2500VAC
Degree of Protection:
IP 20 for QBx0008 - QBx0044 ; IP 00 for QBx0058 – QTx1100
Pollution Degree:
3
EMC
Emissions:
EN 61000-6-4 CISPR 11 Class A
Immunity:
EN 61000-6-2 ESD 8KV air, IEC 801-2;
Electric RF field 10 V/m, 20-1000Mhz, IEC 801-3
Fast transients 2KV, IEC 801-4
Safety:
UL508C
Rated Operational Current
AC:53a:3.5-30: 50-4
Normal Service Conditions:
Altitude:
Up to 1000m.
Humidity:
95% at 50°C or 98% at 45°C
Fan and Control Consumption Ratings:
QBx0008 to QBx0170: No fan
Total approximate consumption: 35VA
QBx0210 to QBx0477: Fans 50 VA
Total approximate consumption: 85VA
QBx0515 to QBx0840 : Fan 50 VA
Total approximate consumption: 100VA
QBx0960 to QBx1100 : Fans 110 VA
Total approximate consumption: 160VA