GE Industrial Solutions Spectra Series Power Panelboards AFP6SKS User Manual
Spectra series™ power panelboards, General, Installation

g
Spectra Series™ Power Panelboards
Filler Plate Kit AFP6SKS
WARNING:
Danger of electrical shock or injury.
Turn
OFF power ahead of the panelboard or
switchboard before working inside the
equipment or removing any component
.
Do
not remove circuit protective devices or any
other component until the power is turned
OFF.
General
These instructions apply to the following catalog numbers:
•Filler plate kit AFP6SKS
•Circuit breaker types TKM, THKM, TK4V, TKL4V,
SKHA, SKLA, and SKPA
Installation
1. Install circuit breaker.
Install the circuit breaker
according to instruction sheet GEH-5623 for plug-in
construction or DEH-061 for bolt-on construction.
2. Install end filler plates.
For type TKM, THKM,
TK4V, TKL4, SKHA, SKLA, and SKPA circuit
breakers, place the lug covers, as listed in Table 1, on
the line and load ends of the circuit breaker, as
shown in Figure 1. Attach the end filler plates, as
listed in Table 2, to each side of the circuit breaker
with the #10-32 x
9
/
16
" screws provided. Tighten the
screws to 15 in-lb.
Breaker Type
Lug Cover
TKM, THKM
455C592P1, furnished with kit
TK4V, TKL4V
455C592P2, furnished with kit
SKHA, SKLA
Use covers furnished with breaker
SKPA*
Use covers furnished with breaker
* SKPA is available in 44"-wide panelboard or 45"-wide
switchboard construction only.
Table 1. Lug covers used with each breaker type.
Filler Plate
Switchboard or Panelboard
252B1768G2
40"-wide panelboard or switchboard
252B1768G1
44"-wide panelboard
252B1768G1
45"-wide switchboard
Table 2. End filler plates used with each panelboard or switchboard.
Figure 1. Installation of lug covers and filler plates.
GEH5629 Installation Instructions
R05
Filler
Plate
Filler
Plate
Lug
Cover
Lug
Cover
#10-32 Screws