GE Industrial Solutions SDCJBB User Manual
Distribution cable junction box, Deh-006 installation instructions, Ge energy industrial solutions
![background image](/manuals/294971/1/background.png)
Overview
The General Electric Distribution Cable Junction Box
is a modular connector used to provide quick, easy
and reliable attachment of Spectra
®
RMS Molded-
Case Circuit Breakers with microEntelliGuard
TM
,
MicroVersaTrip
®
PM or Plus Trip Units to the Distribution
Cable System. The electronic signals supported by the
Distribution Cable Junction Box vary depending on
the type of Molded-Case Circuit Breaker used; a list of
supported functions appears below.
Input signals to Spectra
®
RMS Breaker with
MicroVersaTrip
®
PM Trip Unit
• control power (+24vdc)
• control power (common)
• system communications (Comm +)
• system communications (Comm –)
• breaker position (via installed aux. switch - red wire)
• breaker position (via installed aux. switch - white wire)
• voltage A f (must be from Voltage Module or Voltage
Conditioner Plate or Voltage Conditioner Assembly)
• voltage B f (must be from Voltage Module or Voltage
Conditioner Plate or Voltage Conditioner Assembly)
• voltage C f (must be from Voltage Module or Voltage
Conditioner Plate or Voltage Conditioner Assembly)
• neutral current sensor - black (for equipment ground
fault)
1
• neutral current sensor - white (for equipment ground
fault)
1
Input signals to Spectra
®
RMS Breaker with
MicroVersaTrip
®
Plus Trip Unit
• control power (+24vdc)
• control power (common)
• neutral current sensor - black (for equipment ground
fault)
1
• neutral current sensor - white (for equipment ground
fault)
1
Input signals to Spectra
®
RMS Breaker with
microEntelliGuard
™
Trip Unit
• control power (+24vdc)
• control power (common)
• system communications (Comm +)
• system communications (Comm –)
• breaker position (via installed aux. switch - red wire)
• breaker position (via installed aux. switch - white wire)
• voltage A f (must be from Voltage Module or Voltage
Conditioner Plate or Voltage Conditioner Assembly)
• voltage B f (must be from Voltage Module or Voltage
Conditioner Plate or Voltage Conditioner Assembly)
• voltage C f (must be from Voltage Module or Voltage
Conditioner Plate or Voltage Conditioner Assembly)
• neutral current sensor - black (for equipment ground
fault)
1
• neutral current sensor - white (for equipment ground
fault)
1
DEH-006 Installation Instructions
Distribution Cable Junction Box
For Spectra
®
RMS Molded-Case Circuit Breakers with microEntelliGuard
TM
Trip Units,
MicroVersaTrip
®
PM Trip Units or MicroVersaTrip
®
Plus Trip Units
For Catalog Number SDCJBB
Circuit Breaker Accessory
GE Energy
Industrial Solutions
1
Neutral current sensor input is required for 3 PH/4W or 1 PH/3W systems. For 3
PH/3W systems, do not make any connections.