GE Industrial Solutions Spectra Series Power Panelboards Ground Fault Neutral, 1200 A Maximum User Manual
Spectra series™ power panelboards, Installation, Ground fault neutral, 1200 a maximum

g
Spectra Series™ Power Panelboards
Ground Fault Neutral, 1200 A Maximum
WARNING: Danger of electrical shock or injury.
Turn
OFF power ahead of the panelboard or
switchboard before working inside the
equipment or removing any component
.
Do
not remove circuit protective devices or any
other component until the power is turned
OFF.
Installation
1. Remove the connection bar. Loosen the four nuts on
the studs (two in each strap) located at the current
transformer and at the load end of the neutral, as
shown in Figure 1. Slide out the connection bar
assembly.
Figure 1. Removing the connection bar assembly.
2. Mount the neutral. Place the neutral in the desired
position in the end of the box stamped
LINE.
Mount it
on the studs in the back of the box. as shown in Figure
2. Place a flat washer, lock washer, and nut on the
studs, as shown in Figure 3. Leave the nuts hand tight.
Align the elongated holes in the neutral with the
holes in the box and secure with eight #10-32 x
7
/
8
"
thread-forming screws, as shown in Figure 4. Tighten
the screws and nuts to 27–32 in.-lb.
Figure 2. Neutral mounting position.
GEH5683 Installation Instructions
R02
Connection
Bar
Nuts
Current
Transformer
Load End
of Neutral
Stud (one
each side)