GE Industrial Solutions EntelliGuard G Shunt Trip (Extended Range) User Manual
Entelliguard, G circuit breaker, Accessories

Introduction
Shunt Trip (Extended Range):
A device designed to switch the Power Circuit
Breaker OFF remotely. When energized a Shunt
Release instantaneously activates the circuit
breaker mechanism ensuring a rapid
disconnection of the main contacts. Shunt trips
are suitable for a continuous power supply and
are designed to be used as a closure prevention
device when energized. Two Shunt trips can be
mounted in each Power Circuit Breaker. The
device is available as factory mounted
component or as a field mountable device. It is an
easy-to-fit, clip-on unit, with simple plug-in
connectors to the Secondary Disconnect Block.
Table 1.Catalog Numbers and Ratings
Catalog No.
DC
Voltage AC Voltage
GSTG024R
24V
GSTG048R
48V
48V
GSTG072R
70-72V
GSTG120R
110-125V
120-127V
GSTG208AR
208V
GSTG240R
220V
240V
GSTG250DR
250V
DEH-41411 Installation Instructions
EntelliGuard
®
G Circuit Breaker
Accessories
Shunt Trip (Extended Range)
WARNING: Before installing any accessories, turn the
breaker OFF, disconnect it from all voltage sources,
and discharge the closing spings.
Inrush Power: 480VA
Steady state : 50VA
Use the following procedure to install the Shunt
Trip accessory into the circuit breaker.
1. Verify that the rating on the Shunt Trip
Mechanism identification plate matches the
voltage rating required for the application, as
listed in Table 1.
2. Turn the breaker off and discharge the closing
springs by depressing the OFF and ON buttons in
the sequence OFF-ON-OFF. Verify that the
breaker OFF-ON indicator shows OFF on a green
background and that the charge indicator shows
DISCHARGE on a white background. If installing
in a draw-out type breaker remove breaker from
adaptor (cassette) before continuing.
AVERTISSEMENT: Avant d’installer tout accessoire,
mettre le disjoncteur en position OFF, le déconnecter
de toute tension d’alimentation , et décharger les
resorts d’armement
3. Loosen the 6 screws on front cover (fascia)
using a posidrive screw driver as shown in Fig 1.B
Rotate the charging handle down and slide the
front cover over the handle to remove the front
cover as shown in Fig. 1.C