beautypg.com

GE Industrial Solutions EntelliGuard E Bell Alarm with Lockout for 3200–5000 Ampere User Manual

Page 2

background image

plunger and locating pin fit in the appropriate holes.

The label on the end of the module appears as in

Figure 4, with the legend

LF LO

horizontal. Attach

the module with the two screws provided.

8. Run the wires from the Bell Alarm module to the

secondary disconnect, as illustrated in Figure 5.

Attach the wires to the breaker frame with wire ties,

as indicated. Table 1 lists the wire colors and

terminal numbers. Figure 6 shows the secondary

disconnect terminal numbering scheme, as seen

from the front of the breaker, with the Bell Alarm

terminals in bold.

Figure 2. Installation of the Bell Alarm with Lockout.

Figure 3. Top view of the Bell Alarm mounting plate, showing the pin

to engage the breaker mechanism.

Figure 4. Orientation of the label on the Bell Alarm with Lockout

module.

Returning the Breaker to Service

9. Check that the breaker racking mechanism is still in

the

DISC

position. Pull the manual charging handle

out part way, then slide the handle through the slot

in the escutcheon and move the escutcheon into

place. Insert the six mounting screws and tighten to

14–20 in-lb.

10. Replace the trim ring around the escutcheon, with

the narrow side at the bottom. Insert the ends of the

spring loaded rods into the holes in the escutcheon

brackets.

11. Insert the racking handle and return the racking

mechanism to the

DISC

position, as shown by the

draw-out position indicator.

12. Reinstall the breaker into its cubicle or substructure.