plunger and locating pin fit in the appropriate holes.
The label on the end of the module appears as in
Figure 4, with the legend
↑
LF LO
horizontal. Attach
the module with the two screws provided.
8. Run the wires from the Bell Alarm module to the
secondary disconnect, as illustrated in Figure 5.
Attach the wires to the breaker frame with wire ties,
as indicated. Table 1 lists the wire colors and
terminal numbers. Figure 6 shows the secondary
disconnect terminal numbering scheme, as seen
from the front of the breaker, with the Bell Alarm
terminals in bold.
Figure 2. Installation of the Bell Alarm with Lockout.
Figure 3. Top view of the Bell Alarm mounting plate, showing the pin
to engage the breaker mechanism.
Figure 4. Orientation of the label on the Bell Alarm with Lockout
module.
Returning the Breaker to Service
9. Check that the breaker racking mechanism is still in
the
DISC
position. Pull the manual charging handle
out part way, then slide the handle through the slot
in the escutcheon and move the escutcheon into
place. Insert the six mounting screws and tighten to
14–20 in-lb.
10. Replace the trim ring around the escutcheon, with
the narrow side at the bottom. Insert the ends of the
spring loaded rods into the holes in the escutcheon
brackets.
11. Insert the racking handle and return the racking
mechanism to the
DISC
position, as shown by the
draw-out position indicator.
12. Reinstall the breaker into its cubicle or substructure.