GE Industrial Solutions Spectra Series Power Panelboards SE, SF, TE, TF, TQ, and TEL User Manual
Spectra series™ power panelboards, General, Installation

g
Spectra Series™ Power Panelboards
Circuit Breaker Cover
WARNING:
Danger of electrical shock or injury.
Turn
OFF power ahead of the panelboard or
switchboard before working inside the
equipment or removing any component
.
Do
not remove circuit protective devices or any
other component until the power is turned
OFF.
General
These instructions apply to the following circuit breaker
frames: SE, SF, TE, TF, TQ, and TEL.
Installation
1. Select the breaker cover supports and breaker covers.
Table 1 lists the catalog numbers of the appropriate
cover supports for various switchboard and
panelboard sizes. Table 2 lists the breaker covers for
various breaker types.
Switchboard or Panelboard Width
Cover Height
27 & 31" Pnlbd
35" Swbd
36 & 40" Pnlbd
40" Swbd
44" Pnlbd
45" Swbd
4
1
/
8
" (3X) &
5
1
/
2
" (4X)
208C1850P4*
208C1850P3
208C1850P3
2
3
/
4
" (2X)
208C1850P6
208C1850P5
208C1850P5
• Use 208C1850P3 for SFHA, SFLA, SFPA, TFL, TFJ, TFK, and
THFK, in single-branch mountings.
Table 1. Circuit breaker cover support catalog numbers for various
panelboard and switchboard widths.
Switchboard or Panelboard Width
Cover Height
27 & 31" Pnlbd
35" Swbd
36 & 40" Pnlbd
40" Swbd
44" Pnlbd
45" Swbd
SEDA, SEHA, SELA, SEPA – Double-branch mount only
4
1
/
8
" (3X)
208C4262G32
208C4262G33
208C4262G34
5
1
/
2
" (4X)
N/A
208C4262G35
208C4262G36
SFHA, SFLA, SFPA – Single-branch mount (see Figure 1)
4
1
/
8
" (3X)
208C4262G53
208C4262G54
208C4262G55
5
1
/
2
" (4X)
N/A
208C4262G56
208C4262G57
SFHA, SFLA, SFPA – Double-branch mount
4
1
/
8
" (3X)
208C4262G58
208C4262G59
208C4262G60
51/2" (4X)
N/A
208C4262G61
208C4262G62
TEB, TED, THED, TEL – Double-branch mount
2
3
/
4
" (2X)
208C4262G26
208C4262G27
208C4262G28
4
1
/
8
" (3X)
208C4262G29
208C4262G30
208C4262G31
TFJ, TFK, THFK, TFL – Single-branch mount (see Figure 1)
4
1
/
8
" (3X)
208C4262G1
208C4262G2
208C4262G3
TFJ, TFK, THFK, TFL – Double-branch mount
4
1
/
8
" (3X)
N/A
208C4262G6
208C4262G7
TQD, THQD – Double-branch mount
2
3
/
4
" (2X)
208C4262G20
208C4262G21
208C4262G22
4
1
/
8
" (3X)
208C4262G23
208C4262G24
208C4262G25
Table 2. Circuit breaker cover catalog numbers for various
panelboard and switchboard widths.
2. Mount the circuit breaker cover supports.
Mount the
breaker cover supports supplied in the kit to the
circuit breaker module or mounting plate, according
to the instructions supplied with the module or
mounting plate.
To install the cover support for single-branch SF and
TF breakers, first remove the breaker mounting
bracket by prying back the plastic spring clip on the
module. Slide the cover support on and snap the
breaker mounting bracket back into the module.
Fasten the cover support to the module, as shown in
Figure 1.
Figure 1. Installing the cover support for single-branch SF and TF
breakers.
3. Attach the center barrier
to the breaker cover for
double-branch 3X or 4X TEB, TED, THED, TQD,
THQD, SE, SF, TFK, THFK, and TFL breakers. Use
two push-in rivets, as shown in Figure 2.
Figure 2. Attaching the center barrier to the breaker cover.
DEH042 Installation Instructions
R03
Cover
Support
Breaker
Mounting
Bracket