GEH-6254 Installation Instructions
Connections
The screw terminals on the Voltage Conditioner
Assembly are labeled by function for clarity. The
terminal strip pocket will accommodate a spade
lug or ring terminal with a tongue width up to 0.320
inches. The terminal screw size is 10-32. To make the
Connection, attach an appropriate spade lug or ring
terminal to the wire, then slip the fastener beneath the
terminal screw and tighten.
The Voltage Conditioner Assembly also contains two
12-pin plug connectors. The connectors are keyed so
they cannot be inserted incorrectly into a mating 12-
pin receptacle connector. To connect to the Voltage
Conditioner Assembly plug(s), align the receptacle
interlock connector of a Distribution Cable Harness with
the plug hook connector of the Voltage Conditioner
Assembly. Insert the receptacle until the interlock and
hook catch (see Figure 5).
To disconnect from the Voltage Conditioner Assembly,
press down at the rear of the receptacle interlock until
the interlock clears the plug hook and withdraw the
receptacle interlock (see Figure 6).
Figure 5. Slide view of receptacle-plug insertion into
the Voltage Conditioner Assembly.
Figure 6. Side view of receptacle-plug removal from
the Voltage Conditioner Assembly.
PARTS AND OPTIONS
There are no user-serviceable components or parts
within the Voltage Conditioner Assembly; however, in
order for the unit to be properly protected, the fuses
and fuse holders listed in Table 3 are recommended for
use with the Voltage Conditioner Assembly (connect to
the primary side of the three potential transformers).
Table 4 contains a list of potential transformers that
are recommended for use with the Voltage Conditioner
Assembly (all units rated 120Vac on the secondary
and are rated 1-VA @ 60Hz with 0.2% on magnitude
accuracy). These potential transformers must always
be protected. It is recommended that the primary side
of the potential transformer be fused with the fuses
previously described.
If it is preferred to purchase a voltage-sensing
accessory that has factory-mounted AC line fuses and
three 1-VA @ 60Hz accuracy potential transformers,
Table 5 contains a listing of GE Voltage Conditioner
Plates. These Voltage Conditioner Plates contain the
Voltage Conditioner Assembly as an integral part
of the plate and are factory-wired from the Voltage
Conditioner Assembly to the three 1-VA potential
transformers and to the fuses holders (one set of fuses
is included).
Table 3. Recommended replacement fuses for use with the Power
Supply Assembly.
Class CC Current limiting Fuse
Fuse Holder
Gould-Shawmut ATMR 2
Gould-Shawmut 3012R & DFC3M
Table 4. Recommended potential transformers for use with the
Voltage Conditioner Assembly.
Primary Rating
Transfab Inc. Catalog Number
120Vac
DL7027EE
208Vac
DL7026FE
240Vac
DL7029GE
277Vac
DL7030LE
480Vac
DL7025OE
600Vac
DL7028QE
Table 5. Available Voltage Conditioner Plates.
Catalog Number
Source Voltage Rating
Comments
SVCA120Y
120Vac Wye connection
f to N potential
SVCA208Y
208Vac Wye connection
f to f potential
SVCA240D
240Vac Delta connection
f to f potential
SVCA277Y
277Vac Wye connection
f to N potential
SVCA480Y
480Vac Wye connection
f to f potential
SVCA480D
480Vac Delta connection
f to f potential
SVCA600D
600Vac Delta connection
f to f potential