3 inductive operation series circuit, 4 inductive operation lead-lag circuit – OSRAM DULUX F User Manual
Page 35
Economical long-life light sources with plug-in bases
Compact Fluorescent Lamps OSRAM DULUX
®
Technical Guide
33
2.2.3 Inductive operation Series circuit
Series circuits (tandem circuits) are possible only for certain types of lamps in which the arc voltage
does not exceed certain values (see 3.2.1 Permissible lamp/CCG combinations and system data,
p. 47).
Measurement conditions according to IEC 60901:
220 V / 50 Hz supply voltage1)
Operation on reference gear
Ambient temperature 25°C
Lamps aged 100 hours
Base-up position for OSRAM DULUX
®
S
Horizontal position for OSRAM DULUX
®
L, F
Lamp
reference
Luminous
flux
lm
Lamp
Wattage
W
Luminous
efficacy
lm/W
Arc
Voltage
V
Lamp
current
mA
Calibra-
tion
current
mA
Impe-
dance
Power
factor
2x DULUX
®
S 5W
515
11
-
35
180
170
1070
0.12
2x DULUX
®
S 7W
820
13.7
-
47
160
170
1070
0.12
2x DULUX
®
S 9W
950
14.4
-
60
130
170
1070
0.12
2x DULUX
®
L 18W (XT)
2500
38
-
58
425
370
390
0.12
2x DULUX
®
F 18W
2300
38
-
56
425
370
390
0.12
1)
In accordance with IEC 60901, measurements are taken at 220 V/50 Hz on the reference control gear. However, there is no change in the
electrical lamp data for 230 V and 240 V supplies, provided suitable control gear is used.
2.2.4 Inductive operation Lead-lag circuit
With certain lamps in two-lamp inductive arrangements, a lead-lag circuit can be set up in which
one of the two CCGs is combined with a series capacitor. For the capacitor data see 3.2.2
Compensation.
Circuit diagram available a