REVERSING DRYER CONTROLLER FACTORY DEFAULT PROGRAM

SETTINGS

DRY

CYCLE

DRYER

DIRECTION

COOL

DOWN

TIME

(MINUTES)

TOTAL
CYCLE

TIME

(MINUTES)

DRYING

TEMPERATURE

(

0

F) (

0

C)

DRYER LOAD

1 REV.

5

35 180

82

Towels, pads,

heavy cotton

2 REV.

2

20 170

77

Sheets, blended

materials

3 REV.

5

25 180

82

Cotton

4 NON-REV.

2

20

130 54

Synthetic

materials

5 NON-REV.

2

25

175 79

Blended materials


REVERSING DRYER FAULT CODES

FAULT#

FAULT

DESCRIPTION

ACTION

F1

Shorted thermostat

sensor.

Dryer stops and “F1” flashes on the 4-digit display. When

short circuit on sensor input is removed, “LOAd” appears

on the 4-digit display and the remaining dry time is reset.

F2

Open thermostat

sensor.

Dryer stops and “F2” flashes on the 4-digit display. When

a good sensor is connected to sensor input, “LOAd”

appears on the 4-digit display and the remaining dry time

is reset.

F3 EEPROM

corrupted.

Dryer will not start and “F3” appears on the 4-digit

display. The power to the dryer must be cycled to reset

the controller. Fault should only occur when starting a dry

cycle.

F4

Gas valve on fault.

The drying temperature did not increase 1

O

F. in 5 minutes.

“F4” will flash on the display and the dry cycle will finish

without calling for heat (energizing gas valve). Opening

the door or pressing the STOP key will reset the fault and

clear the remaining time in the dry cycle.

F5 Temperature

fault.

The drying temperature is at least 25

O

F. above the

temperature setting. “F5” will flash on the 4-digit display

and the dry cycle will finish without calling for heat

(energizing the gas valve). The power to the dryer must

be cycled to reset the controller.