CG Series
High Flux Brackish Water RO Elements (Cellulose Acetate)
The C-Series family, a triacetate/diacetate blend,
has a higher flux and better mechanical stability
than standard cellulose acetate. C-Series elements
offer an increased chlorine resistance compared to
thin-film elements.
CG High Flux Elements are used for brackish water
desalination and process stream concentration.
Table 1: Element Specification
Membrane
C-series, cellulose acetate
Model
Average
permeate flow
gpd (m3/day)
1,2
Average NaCl
rejection
1,2
Minimum NaCl
rejection
1,2
CG8040F
7,300 (27.6)
93.0%
85.0%
1
Average salt rejection after 24 hours operation. Individual flow rate may vary
+25%/-15%.
²Testing conditions: 500 ppm NaCl solution at 210 psi (1,448 kPa) operating pres-
sure, 77°F, pH 6.5 and 15% recovery.
Model
Active area
ft
2
(m
2
)
Outer wrap
Part
number
CG8040F
350 (32.5)
Fiberglass
1206896
Figure 1: Element Dimensions Diagram - Female
Model²
Dimensions, inches (cm)
Boxed
A
B
1
C
3
Weight
lbs (kg)
CG8040F
40.0
(101.6)
1.125
(2.86)
7.9
(20.1)
32
(14.5)
1
Internal diameter unless specified OD (outside diameter).
²These elements are dried then bagged before shipping.
3
The element diameter (dimension C) is designed for optimum performance in GE
pressure vessels. Others pressure vessel dimension and tolerance may result in
excessive bypass and loss of capacity.
Table 3: Operating and CIP parameters
Typical Operating Pressure
60-200 psi (414-1,379 kPa)
Typical Operating Flux
10-18 GFD (17-30 LMH)
Maximum Operating Pressure
450 psi (3,103 kPa)
Maximum Temperature
Continuous operation: 86°F (30°C)
Clean-In-Place (CIP): 86°F (30°C)
pH Range
Continuous operation: 5.0-6.5,
Clean-In-Place (CIP): 3.0-8.0
Maximum Pressure Drop
Over an element: 12 psi (83 kPa)
Per housing: 50 psi (345 kPa)
Chlorine Tolerance
1 ppm maximum continuous
30 ppm for 30 min. during sanitization
Feedwater
NTU < 1
SDI < 5