beautypg.com

General properties – GE P&W Mobile Water Treatment Systems - Mobile Membrane Microfiltration System User Manual

Page 2

background image

Page 2

FS1682EN Aug-07

General Properties

Trailer

Length:

48’-0” (14.6 meters)

Height:

13’-6” (4.1 meters)

Width:

8’-3” (2.5 meters)

Gross operating weight (approx.):

57,000 lbs. (25,9i00 kg)

Gross shipping weight (approx.):

30,700 lbs. (13,900 kg)

Connections

Connection Type:

Victaulic/Flange

Inlet:

8 inch (200 mm)

Outlet (Filtrate):

8 inch (200 mm)

Backwash Waste:

8 inch (200 mm)

Misc. Waste:

3 inch (75 mm)

Electrical

Service:

480 VAC, 3 phase

Breaker size:

250 amp

Installed KVA:

148 KVA

Heating:

Climate controlled via standard
electric HVAC

PLC

Instrumentation

Parameter

Inlet

Outlet

GE Fanuc PLC

Flow

X

X

Pressure

X

X

Temperature

X

Turbidity

X

X

Analog (4-20 mA) to customer
tie-in and/or discrete tank level
for automatic shut down and
control

System on Board

Membrane:

PVDF Hollow Fiber Membrane

Air Compressor:

Provides instrument air

Max. Water Temp.:

104ºF (40ºC)

Min. Water Temp.:

32ºF (0ºC)

Inlet Pressure:

30 psig (2 bar) to 45 psig (3 bar)

Min. Inlet Pressure:

5 psig (.3 bar)

Outlet Pressure:

30 psig (2 bar) to 90 psig (6.1 bar)

Max. Inlet Turbidity:

100 NTU/peak to 500 NTU

Maximum Inlet Water TSS:

300 mg/l

Influent Flow:

Up to 1100 gpm (250 m

3

/hr)

Effluent Flow:

Up to 800 gpm (181 m

3

/hr) continuous

Waste Flow:

5 gpm (1.1 m

3

/hr) max. intermittent

Effluent Turbidity:

<0.05 NTU maximum, <0.2 NTU typical

SDI:

<3 maximum, <2.5 typical