beautypg.com

GE P&W E-Series Reverse Osmosis - EZ-2 Kit 50 Hz User Manual

Ez2 kit, 50 hz, General properties

background image

Fact Sheet

Find a contact near you by visiting www.gewater.com and clicking on “Contact Us”.

* Trademark of General Electric Company; may be registered in one or more countries.

©2013, General Electric Company. All rights reserved.

FS1138EN.doc Jul-13



EZ2 Kit, 50 Hz

Reverse Osmosis Machine 1.7-9.6 cubic meters per day

Figure 1: EZ2 Kit

When you mention reverse osmosis (RO), GE Water
& Process Technologies is the first name to come to
mind. Our E-series RO machines (Figure 1) are de-
signed for durable operation, high quality product
water production, easy installation and straightfor-
ward control.

General Properties

Typical Applications

Process ingredient water

Safe drinking water

Spot free rinse water

Ion exchange pre-treatment

R & D lab use

Standard Economy Features

1-micron pre-filter

Automatic inlet shut-off valve

Remote machine on/off capability

Operating pressure gauge

Flow control center including concentrate and
recycle valves

Brass pump

Deluxe (DLX) Features – In addition to ECN
Features

Low inlet pressure switch

Conductivity meter

Stainless steel pump

Permeate and concentrate flow meters

Table 1: Operating Parameters

Operating Pressure

14-15 bar

Maximum Recovery

50%

Nominal Rejection

95-98%

Operating Temperature

13-30°C (55-86°F)

Minimum Inlet Pressure

2 bar

Design Temperature

25°C (77°F)