beautypg.com

GE P&W Spiral Wound Membranes - AG HR LF Series User Manual

Ag hr lf series, Fact sheet

background image

Fact Sheet

Find a contact near you by visiting www.gewater.com and clicking on “Contact Us”.

* Trademark of General Electric Company; may be registered in one or more countries.

©2013, General Electric Company. All rights reserved.

FSpwAG-HR_LF_EN Dec-13


AG HR LF Series

High Rejection Low Fouling Brackish Water RO Elements

The A-Series family of proprietary thin-film reverse
osmosis membrane are characterized by high flux and
high sodium chloride rejection. AG HR LF Brackish
Water Elements are selected for the treatment of im-
paired water when high rejection is desired. The AG
HR LF membrane features a more neutral charge and
therefore reduces interactions with potential foulants
present in surface water or tertiary effluent.

Table 1: Element Specification

1

Average salt rejection after 24 hours operation. Individual flow rate may

vary +25%/-20%.

2

Testing conditions: 2,000ppm NaCl solution at 225psi (1,550kPa) operating

pressure, 77°F (25°C), pH7 and 15% recovery.

Model

Active area

ft

2

(m

2

)

Outer wrap

Part

number

AG-90 LF

90 (8.4)

Fiberglass

3056674

AG-400 LF

400 (37.2)

Fiberglass

3042540

AG-400 LF, 34

400 (37.2)

Fiberglass

3056675

AG-440 LF

440 (40.9)

Fiberglass

3056676





Table 2: Operating and CIP parameters

3

SDI is measured on a non-linear scale using a 0.45 micron filter paper.

Additionally, finer colloids, particulates and microorganisms that pass
through the filter paper and not measured in the SDI test, will potentially
foul the RO element. For performance consistency and project warranty,
please use Winflows projection software and consult your Filters with
Membranes representative.

Figure 1a: Element Dimensions Diagram – Male






Figure 1b: Element Dimensions Diagram – Female







Table 3: Dimensions and Weights

Model

1

Type

Dimensions, inches (cm)

Boxed

A

B

2

C

Weight

lbs (kg)

AG-90 LF

Male

40.0 (101.6)

0.75 (1.90)

3.9 (9.9)

9 (4)

AG-400 LF

Female 40.0 (101.6) 1.125 (2.86)

7.9 (20.1)

35 (16)

AG-400 LF, 34 Female 40.0 (101.6) 1.125 (2.86)

7.9 (20.1)

35 (16)

AG-440 LF

Female 40.0 (101.6) 1.125 (2.86)

7.9 (20.1)

35 (16)

Model

Average

permeate

flow gpd

(m

3

/day)

1,2

Average NaCl

rejection

1,2

Minimum NaCl

rejection

1,2

AG-90 LF

2200 (8.3)

99.8%

99.3%

AG-400 LF

10500 (39.7)

99.8%

99.3%

AG-400 LF, 34

10500 (39.7)

99.8%

99.3%

AG-440 LF

11500 (43.5)

99.8%

99.3%

Membrane

Thin-film membrane (TFM*)

Typical Operating Pressure

200 psi (1,380 kPa)

Typical Operating Flux

10-20GFD (15-35LMH)

Maximum Operating Pressure 600 psi (4,137 kPa)
Maximum Temperature

Continuous operation: 122°F (50°C)
Clean-In-Place (CIP): 122°F (50°C)

pH range

Optimum rejection: 7.0-7.5,
Continuous operation 4.0-11.0,
Clean-In-Place (CIP): 2.0-11.5

Maximum Pressure Drop

Over an element: 12 psi (83 kPa)
Per housing: 50 psi (345 kPa)

Chlorine Tolerance

1,000+ ppm-hours,
dechlorination recommended

Feedwater

3

NTU < 1
SDI < 5