beautypg.com

Process flow diagram – GE P&W Mobile Water Treatment Systems - ZeeWeed Mobile Water Treatment System User Manual

Page 2

background image

Page 2

TS-MWTS-Mobile-EN-0107-NA GE Logo Mar-08

Standard Features:

Membrane Module

ZeeWeed 500 (NSF Certified)

Membrane Type

Reinforced, low pressure, immersed hollow fi-
ber

Permeate Flow Path

Outside-in

Nominal Pore size

0.04 microns

Membrane

Membrane material

PVDF

Configuration

1 train with 4 cassettes, 26 modules per cas-
sette

Dimensions

40’L x 8.0'W x 9.5’H (40’(12m) HC ISO Container)
12.2m L x 2.5m W x 2.9m H

Membrane tank

316 Stainless Steel

Process piping

316 Stainless Steel

MIT (membrane integrity test)

Yes

Automatic backpulse cleaning

Yes

LT2 compliance

Yes

Process tank volume

4,800 gal; 18,168 L

Clean in Place (CIP) tank volume

1,184 gal; 4,481 L

Weight, shipping/operating

55,000 / 130,000 lbs (24,950 / 58,970 kg)

Aeration scour

Blower self-contained

Control - Interface

Allen Bradley PLC with Transduction PC (HMI)

Instrumentation

Feed and permeate turbidimeters and perme-
ate particle counter

Data Collection System

ZenoTrac™

System

Technical support 24/7

Yes

Overhead clearance

12 ft (3.66 m) minimum

Surrounding access

5 ft (1.5 m) minimum

Electrical

460V/3ph/60Hz/236 amps

Raw water pressure

5 psig (34.5 kPa) minimum
20 psig (138 kPa) maximum

Requirements

Raw water screening

< 1 mm

Process Flow Diagram


Average Feed Water Characteristics

Source Parameters Permeate
Direct
Filtration

<100 NTU turbidity
<5 mg/L TOC

<0.3 NTU turbidity

Enhanced
Coagulation

<100 NTU turbidity
>5 mg/L TOC*

<0.3 NTU turbidity

Settled
Water

<5 NTU turbidity

<0.3 NTU turbidity

Oxidation
(Fe & Mn)

<10 NTU turbidity
<5 mg/L TOC
>1 mg/L Fe,*
>0.3 mg/L Mn*

<0.3 NTU turbidity

Secondary /
Tertiary
Effluent

<100 mg/L TSS

<0.3 NTU turbidity

* Operating parameters to be confirmed with GE membrane solutions under these conditions