Unctional, Iagram, Eliability – B&B Electronics NTPS-24-5 - Datasheet User Manual
Page 7: 24v, 5a, s

CS5.241, CS5.241-C1, CS5.241-S1
C–Series
24V, 5A, S
INGLE
P
HASE
I
NPUT
Dec. 2006 / Rev. 1.3 DS-CS5.241-EN
All parameters are specified at 24V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
7/20
10. F
UNCTIONAL
D
IAGRAM
Fig. 10-1 Functional diagram
+
+
-
-
V
OUT
Input Fuse
&
Input Filter
Output
Voltage
Regulator
Power
Converter
Output
Filter
DC
ok
L
N
Output
Over-
Voltage
Protection
Input
Rectifier
&
Inrush
Limiter
115/230V
Auto Select
11. R
ELIABILITY
AC 100V
AC 120V
AC 230V
Lifetime expectancy
min.
52 000h
58 000h
72 000h
40°C, 24V, 5A
min.
27 000h
34 000h
42 000h
40°C, 24V, 6A
min.
135 000h
128 000h
144 000h
40°C, 24V, 2,5A
min.
142 000h
15 years
15 years
25°C, 24V, 5A
MTBF SN 29500, IEC 61709
638 000h
661 000h
869 000h
40°C, 24V, 5A
542 000h
562 000h
739 000h
40°C, 24V, 6A
1 077 000h
1 111 000h
1 495 000h
25°C, 24V, 5A
MTBF MIL HDBK 217F
552 000h 546
000h 574
000h
40°C, 24V, 5A, Ground Benign GB40
497 000h
491 000h
517 000h
40°C, 24V, 6A, Ground Benign GB40
788 000h
775 000h
800 000h
25°C, 24V, 5A, Ground Benign GB25
The Lifetime expectancy shown in the table indicates the operating hours (service life) and is determined by the
lifetime expectancy of the built-in electrolytic capacitors.
Lifetime expectancy is specified in operational hours. Lifetime expectancy is calculated according to the capacitor’s
manufacturer specification. The prediction model allows a calculation of up to 15 years from date of shipment.
MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates
reliability of a device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily
represent the life of a product.