beautypg.com

Unctional, Iagram, Eliability – B&B Electronics NTPS-24-5 - Datasheet User Manual

Page 7: 24v, 5a, s

background image

CS5.241, CS5.241-C1, CS5.241-S1

CSeries

24V, 5A, S

INGLE

P

HASE

I

NPUT

Dec. 2006 / Rev. 1.3 DS-CS5.241-EN
All parameters are specified at 24V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.

www.pulspower.com Phone +49 89 9278 0 Germany

7/20

10. F

UNCTIONAL

D

IAGRAM

Fig. 10-1 Functional diagram

+

+

-

-

V

OUT

Input Fuse
&
Input Filter

Output

Voltage

Regulator

Power

Converter

Output

Filter

DC

ok

L

N

Output

Over-

Voltage

Protection

Input
Rectifier
&
Inrush
Limiter

115/230V

Auto Select

11. R

ELIABILITY

AC 100V

AC 120V

AC 230V

Lifetime expectancy

min.

52 000h

58 000h

72 000h

40°C, 24V, 5A

min.

27 000h

34 000h

42 000h

40°C, 24V, 6A

min.

135 000h

128 000h

144 000h

40°C, 24V, 2,5A

min.

142 000h

15 years

15 years

25°C, 24V, 5A

MTBF SN 29500, IEC 61709

638 000h

661 000h

869 000h

40°C, 24V, 5A

542 000h

562 000h

739 000h

40°C, 24V, 6A

1 077 000h

1 111 000h

1 495 000h

25°C, 24V, 5A

MTBF MIL HDBK 217F

552 000h 546

000h 574

000h

40°C, 24V, 5A, Ground Benign GB40

497 000h

491 000h

517 000h

40°C, 24V, 6A, Ground Benign GB40

788 000h

775 000h

800 000h

25°C, 24V, 5A, Ground Benign GB25

The Lifetime expectancy shown in the table indicates the operating hours (service life) and is determined by the
lifetime expectancy of the built-in electrolytic capacitors.

Lifetime expectancy is specified in operational hours. Lifetime expectancy is calculated according to the capacitor’s
manufacturer specification. The prediction model allows a calculation of up to 15 years from date of shipment.

MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates
reliability of a device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily
represent the life of a product.