beautypg.com

24v, 5a, s – B&B Electronics NTPS-24-5 - Datasheet User Manual

Page 10

background image

CS5.241, CS5.241-C1, CS5.241-S1

CSeries

24V, 5A, S

INGLE

P

HASE

I

NPUT

Dec. 2006 / Rev. 1.3 DS-CS5.241-EN
All parameters are specified at 24V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.

www.pulspower.com Phone +49 89 9278 0 Germany

10/20

EMC Emission

EN 61000-6-4

Generic standards

Conducted emission

EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22

Class B, input lines

EN 55022

Class A, output lines

Radiated emission

EN 55011, EN 55022

Class B

Harmonic input current

EN 61000-3-2

>2.7A output current not fulfilled

Voltage fluctuations, flicker EN

61000-3-3

fulfilled

This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.

Above an average output current of 2.7A, the harmonic current standard EN61000-3-2 is not fulfilled.

Please note:

A power supply has to comply with EN 61000-3-2 (Standard for harmonic input current) when:
1) the end-device is used within the European Union and
2) the end-device is connected to a public mains supply with a nominal voltage

≥ 220Vac and

3) the power supply is:
- fitted in an end-device with an average input power in excess of 75W or
- fitted in an end-device with a continuous input power in excess of 75W or
- part of a lighting system.

Exceptions:

End-devices for professional applications with an input power > 1000W do not need to fulfill EN 61000-3-2.

Comments:
- The average input power must be determined in accordance with EN 61000-3-2.
- Industrial mains supplies with their own transformer are considered to be “non-public”.
- Where individual self-contained items of equipment are installed in a rack or case
(e.g. devices connected in parallel), they are regarded as being individually connected to the
mains supply. The rack or case need not be tested as a whole. Alternatively it is also permitted
to assess the whole rack or case. This is recommended for devices used in professional
applications with an input power greater than 1000W.