Ac-i, Nput, 24v, 5a, s – B&B Electronics NTPS-24-5 - Datasheet User Manual
Page 3

CS5.241, CS5.241-C1, CS5.241-S1
C–Series
24V, 5A, S
INGLE
P
HASE
I
NPUT
Dec. 2006 / Rev. 1.3 DS-CS5.241-EN
All parameters are specified at 24V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
3/20
5. AC-I
NPUT
AC
input
nom.
AC 100-120V /
200-240V
auto-select input, TN-, TT-, IT-Mains, see
Fig. 5-1
AC input range
90-132Vac
100-120V range, continuous operation
180-264Vac
200-240V range, continuous operation
85-90Vac
Short term or with output derating
264-300Vac <
0.5s
Input
frequency
nom.
50 – 60Hz
±6%
AC 100V
AC 120V
AC 230V
Input
current
typ.
2.34A
2.05A
1.23A
at 24V, 5A see
Fig. 5-3
Power
factor
*)
typ.
0.58
0.56
0.47
at 24V, 5A see
Fig. 5-1
Crest factor **)
typ.
2,9 3,1 3,7
at
24V,
5A
Start-up
delay
typ.
740ms 900ms 720ms
see
Fig. 5-2
Rise
time
typ.
8ms
8ms
8ms
0mF, 24V, 5A, see
Fig. 5-2
typ.
25ms
25ms
25ms
5mF, 24V, 5A, see
Fig. 5-2
Turn-on
overshoot
max.
400mV 400mV 400mV
see
Fig. 5-2
Turn-on
voltage
typ.
75Vac
75Vac
N / A
steady-state value, see
Fig. 5-1
Shut-down
voltage
typ.
55Vac
55Vac
N / A
steady-state value, see
Fig. 5-1
*)
The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**) The crest factor is the mathematical ratio of the peak value to the RMS value of the input current waveform
Fig. 5-1 Input voltage range
Fig. 5-2 Turn-on behavior, definitions
Tur
n
-on
90V
Rated input ranges
V
IN
P
OUT
264Vac
180V
S
hut
-down
132V
no
harm
from
132 to
180V
Range
100-
120V
Range
200-
240V
Start-up
delay
Rise
Time
Ov
ershoot
- 5%
Output
Voltage
Intput
Voltage
Fig. 5-3 Input current vs. output load
Fig. 5-4 Power Factor vs. output load
6A
1 1.5 2
3
4
0
0.5
1
1.5
2
2.5
3A
Input
Current, typ.
5
Output Current
2.5
3.5
4.5
5.5
230Va
c
120
Vac
100
Vac
6A
1 1.5 2
3
4
0.35
0.4
5
Output Current
2.5
3.5
4.5
5.5
0.45
0.5
0.55
0.6
0.65
Power Factor, typ.
230Vac
120Vac
100Va