All parameters are specified at 24V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.

www.pulspower.com Phone +49 89 9278 0 Germany

12/20

17. S

AFETY

Input / output separation

SELV

IEC/EN 60950-1

PELV

EN 60204-1, EN 50178, IEC 60364-4-41

double or reinforced insulation

Class of protection

I

PE (Protective Earth) connection required

Isolation resistance

> 5MOhm

input to output, 500Vdc

PE resistance

< 0.1Ohm

between housing and PE terminal

Touch current (leakage current)

typ. 0.24mA

100Vac, 50Hz, TN mains

typ. 0.35mA

120Vac, 60Hz, TN mains

typ. 0.40mA

230Vac, 50Hz, TN mains

< 0.36mA

110Vac, 50Hz, TN mains

< 0.53mA

132Vac, 60Hz, TN mains

< 0.60mA

264Vac, 50Hz, TN mains

18. D

IELECTRIC

S

TRENGTH

Fig. 18-1 Dielectric strength

A B C

Type test

60s

2500Vac

3000Vac

500Vac

Factory test

5s

2500Vac

2500Vac

500Vac

Field test

5s

2000Vac

2000Vac

500Vac

A

C

N

L

Input

Earth, PE

Output

-

+

B

Type tests and factory tests:
Conducted by the manufacturer. Do not repeat test in field!
Rules for field test:
Use appropriate test equipment which applies the voltage
with a slow ramp! Connect L and N together as well as all
output poles.

The output voltage is floating and has no ohmic connection to ground.

To fulfill the PELV requirements according to EN60204-1 § 6.4.1, we recommend that either the + pole, the – pole or
any other part of the output circuit shall be connected to the protective earth system. This helps to avoid situations in
which a load starts unexpectedly or can not be switched off any more when unnoticed earth faults occur.