beautypg.com

B&B Electronics MODSCAN32 - Manual User Manual

Page 73

background image

73

Port Control Description

The Modbus Port Configuration Control, (Serial), is used to programatically control the operating
characteristics of a local PC Com port connected to one or more MODBUS slave devices. Use of the Serial
control within a user application is optional. The hardware parameters configured by this control may also
be set by accessing menu items within the modbuss ocx helper application, mbOCXsvr.exe. Once
configured, these parameters will remain in place and be used to initialize the designated COM port each
time a control within modbuss.ocx is started.

Properties

The Serial control exposes the following properties and methods:

Port

The PC COM port identification. (If set to 0, indicates that the connection is to be
made via the first TAPI line device.)

Protocol

MODBUS Transmission Mode (0=RTU, 1=ASCII).

TimeOut

Defines the timeout associated with the protocol for this control. Specified in
milliseconds, this is the amount of time the MODBUS driver waits for a slave
device to respond after polling for data.

BaudRate

Serial Baud Rate setting.
(0=300, 1=600, 2=1200, 3=2400, 4=4800, 5=9600, 6=14400,7=19200)

Parity

Odd, Even or No Parity, (0, 1, or 2).

StopBits

Number of Stop Bits, (0=1, 1=1.5, 2=2).

RTSHandshaking

Enable hardware output flow control using RTS/CTS. The control will ALWAYS
enable RTS prior to transmitting. This property blocks transmission until a CTS is
received from the connected slave.

DTRHandshaking

Enable hardware output flow control using DTR/DSR handshaking.

RTSDelay1

Delay in milliseconds between activation of RTS and transmission of the first
character.

RTSDelay2

Delay in milliseconds after transmitting last character before releasing RTS signal.

PhoneNo

Phone number to dial during Initialize(). Used only for TAPI connections.

Methods


Initialize()

Method which instructs the control to configure the defined port. This method
needs to be controlled programatically if the characteristics of the serial
communications channel change during execution of the application. The use of
the Modbus Port Configuration Control is optional within a program, as the
associated setup parameters may be changed via menu options within
mbOCXsvr and remain valid between executions.

HangupCall()

Method used to disconnect a call.

Events