PRESET MULTIPLE REGISTERS (FUNCTION CODE 16)


Holding registers existing within the controller can have their contents changed via function code 16.
Sixteen bits of data for each register is contained within the message.

ADDR

FUN
C

H.O.
ADDR

L.O.
ADDR

QUANTITY

BYTE
CNT

H.O.
DATA

L.O.
DATA

etc.

ERROR
CHECK
FIELD

11

10

00

87

00

02

04

00

0A

??


The normal response to a PRESET MULTIPLE REGISTERS request is to echo the slave address, function
code, starting address, and quantity of registers set.

ADDR

FUNC

H.O.
ADDR

L.O.
ADDR

QUANTITY

ERROR
CHECK
FIELD

11

10

00

87

00

02

56