Example 1: Get the CANopen slave device’s error status.

Assume that the GW-7433D connects 2 CANopen slaves and with total 10

AI channels

, users can send the follow Modbus TCP command to

get these

two CANopen slaves’ status

.


Query --> 1 2 0 0 0 6 01 04

00

0A

00 02

Response --> 1 2 0 0 0 6 01 04 04

00 00

00 2F

(for Big-endian data type*)

The green word

00 0A

is the address for the CAN error status because

the address 00 00 ~ 00 09 are for AI data. The orange word

00 02

indicates

getting the error status of two slaves. The blue word is 1

st

CANopen slave’s

error status, and

00 00

means no error. The red data is 2

nd

CANopen slave’s

error status, and

00 2F

(47) means the slave has disconnected.

Example 2: Reset the CANopen slave device.

Assume the GW-7433D connects 2 CANopen slaves and with total 8

AO channels

. When users want to reset 2

nd

CANopen slave

, users can send

the follow Modbus TCP command to the GW-7433D and it will send a
CANopen reset command to the slave.

Query --> 1 2 0 0 0 6 01 06

00

09

00 01

(for Big-endian data type*)

Response --> 1 2 0 0 0 6 01 06 00 09 00 01 (for Big-endian data type*)

The address

00

09

is the 2

nd

CANopen slave reset command address

because the 00 08 is 1

st

CANopen slave reset command address and the 00

00 ~ 00 07 are the address for AO channel 0 ~ 7. The command

00 01

is to

reset 2

nd

CANopen slave.

* GW-7433D Modbus data support two kinds of the word data type,

Little-endian and Big-endian, and the Big-endian type is the default type.